9.9.7
User Set Characterization 21 Points (U21)
A total of 21 target points can be set every 0.8 mA intervals. When shipped from the factory, the initial
P0 (4 mA, 0 %), P1 (4.8 mA, 5 %), P2 (5.6 mA 10 %), - - -, P19 (19.2 mA, 95 %), and P20 (20 mA,
100 %). For example, a characteristic curve below can be made through the settings of P1 to P20.
User can change all 21 points or only change partially and exit the menu by pressing <ESC> button.
3 seconds
→
→
→
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
or
→
<UP>/<DOWN>
or
→
To repeat with
identical way.
→
<UP>/<DOWN>
or
→
<UP>/<DOWN>
or
→
To automatically
move after
several seconds.
→
<ESC>
2 times
→
This function is activated by saving the Valve Flow Characterization Curves (CHAR) of above Section
9.9.5 as “U21”.