Smart Positioner
YT-3100
Product Manual
Ver. 1.19
47
9.9.6
User Set Characterization 5 Points (U5)
A total of 5 target positions are set every 4 mA intervals. When shipped from the factory, the initial
positions are P0 (4 mA, 0 %), P1 (8 mA, 25 %), P2 (12 mA, 50 %), P3 (16 mA, 75 %), and P4 (20 mA,
100 %). User can change all 5 points or only change partially and exit the menu by pressing <ESC>
button.
3 seconds
→
→
→
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
or
→
<UP>/<DOWN>
or
→
<UP>/<DOWN>
or
→
<UP>/<DOWN>
or
→
<UP>/<DOWN>
or
→
To automatically
move after
several seconds.
→
<ESC>
2 times
→
This function is activated by saving the Valve Flow Characterization Curves (CHAR) of above Section
9.9.5 as “U5”.