Smart Positioner
YT-2600 series
Product manual
Ver. 1.30
53
RNG ERR
➢
I
ndicated when the feedback lever’s
angle used is excessively small
during auto calibration.
➢
When this error is detected, auto
calibration is aborted and this
message is indicated immediately
on LCD display.
➢
Re-install the positioner by
moving it towards the actuator
stem so that the angle use of the
feedback lever becomes larger.
LEAK
➢
Indicated when movement of
feedback lever is detected without
any pneumatic action of positioner
during auto calibration.
➢
When this error is detected, auto
calibration is aborted and this
message is indicated immediately
on LCD display.
➢
Check for leaks from output port
of the positioner and piping.
PT ERR
➢
Indicated when a leak is detected in
“PT TIME” during AUTO 2 or 3
calibration. Auto calibration will stop
and the error message will display
on the LCD.
➢
Make sure there are no leak in
the out ports of the positioner or
pipe lines
9.2
Error code which is displayed while using the product
Error Code
Code Description and Cause
Action
OVER CUR
➢
Indicated and blinked when 24mA or
more current is detected to the
demand input terminal.
➢
Buttons will not work while this error
message is displayed.
➢
Check the connection status to
the demand input terminal.
(miswiring, overcurrent input, etc.)
Summary of Contents for YT-2600 Series
Page 1: ...SMART POSITIONER PRODUCT MANUAL YT 2600 SERIES VERSION 1 30 Rotork YTC Limited...
Page 4: ...Smart Positioner YT 2600 series Product manual Ver 1 30 4 10 Main Software Map 56...
Page 9: ...Smart Positioner YT 2600 series Product manual Ver 1 30 9 Fig L 3 EAC label...
Page 10: ...Smart Positioner YT 2600 series Product manual Ver 1 30 10 Fig L 4 CCC label...
Page 56: ...Smart Positioner YT 2600 series Product manual Ver 1 30 56 10 Main Software Map...