ITEM
Description
FF / FS
YT-2600L
1’st row→FF: Fail Freeze / FS: Fail Safe.
2’nd row→Positioner model.
1.6.03
VERSION /
2020DC31
1’st row→version number of firmware.
2’nd row→VERSION: Main software version /
2020-12(DC)-31: loading date of software.
(January JA, February FB, March MR, April AR, May MY, June JN, July
JL, August AG, September SP, October OT, November NV, December
DC)
※
You can toggle them, pushing <ENTER>
HART REV
HART protocol version
POL AddR
HART protocol channel address.
※
You can change it, pushing <ENTER>
4.18
0Y 0d
Total used time duration. If a unit was used less than 1 hour, the time
will not accumulate.
1’st row→”4.18” means 4hours and 18minutes.
2’nd row→0Y: years, 0d: days
3.12
FULL OP
Time required (seconds) to fully open the current valve from the closed
state.
Saved after AUTO 2 or AUTO 3 Calibration.
2.97
FULL CL
Time required (seconds) to fully close the current valve from the opened
state.
Saved after AUTO 2 or AUTO 3 Calibration.
VM NOR /
VM dIZ /
VM REV
Display types of valve stroke on LCD.
VM NOR : View Mode Normal. 4 mA
→
0 %, 20 mA
→
100 % display.
VM dIZ : Raw data
VM REV : View Mode Reverse. 4 mA
→
100 %, 20 mA
→
0 % display.
※
You can change it, pushing <ENTER>
Erro
Error code(C, D) or warning code(B, F, G, H).
Refer to 9.1 or 9.2 sections
AbS
Absolute resistance value.
Summary of Contents for YT-2600 Series
Page 1: ...SMART POSITIONER PRODUCT MANUAL YT 2600 SERIES VERSION 1 30 Rotork YTC Limited...
Page 4: ...Smart Positioner YT 2600 series Product manual Ver 1 30 4 10 Main Software Map 56...
Page 9: ...Smart Positioner YT 2600 series Product manual Ver 1 30 9 Fig L 3 EAC label...
Page 10: ...Smart Positioner YT 2600 series Product manual Ver 1 30 10 Fig L 4 CCC label...
Page 56: ...Smart Positioner YT 2600 series Product manual Ver 1 30 56 10 Main Software Map...