Modbus Data Base
Publication PUB091-003-00_0119
47 of 76
7.6.1
Data Accessed with Function Code 01 - Read Coils
Location
(Bit)
R/W
Data
Range
0
R/W
Stop command output coil status
0-1
1
R/W
Close command output coil status
0-1
2
R/W
Open command output coil status
0-1
3
R/W
ESD command output coil status
0-1
4
R/W
DO-1 output coil status
0-1
5
R/W
DO-2 output coil status
0-1
6
R/W
DO-3 output coil status
0-1
7
R/W
DO-4 output coil status
0-1
Note: Coil ‘on’ when the state is true, reports as a ‘1’.
7.6.2
Data Accessed with Function Code 02 - Read Discrete Inputs
Location
(Bit)
R/W
Data
Range
0
RO
Actuator moving
0-1
1
RO
Closed limit
0-1
2
RO
Open limit
0-1
3
RO
Running closed
0-1
4
RO
Running open
0-1
5
RO
Remote selected
0-1
6
RO
Local Stop selected
0-1
7
RO
Local selected
0-1
8
RO
Thermostat tripped
0-1
9
RO
Monitor relay
0-1
10
RO
Valve obstructed
0-1
11
RO
Valve jammed
0-1
12
RO
Valve moving by hand
0-1
13
RO
Moving inhibited
0-1
14
RO
Position control enabled
0-1
15
RO
Watchdog recovery
0-1
16
RO
Battery low
0-1
17
RO
Open interlock active
0-1
18
RO
Close interlock active
0-1
19
RO
DI-1
0-1
20
RO
DI-2
0-1
21
RO
DI-3
0-1
22
RO
DI-4
0-1
23
RO
Slow mode
0-1
Note: When the input is true the status reports as a ‘1’.