No overshoots, most stable, very slow response to input signal to achieve target position.
Dead band
Applicable for Posidapt
–
Modern, Expert, Super, Ultra and IPST
This parameter is used to adjust the dead-band of the controller.
•
Auto -
Factory default
This parameter continuously & adaptively adjusts the dead band to the requirement of the
control loop, if a regulating oscillation is detected.
•
Custom
In other discrete settings the dead band value can be adjusted manually. The value can be
set from 0.1 to 10.0%