Deviation of Set point
Applicable for Posidapt
– Ultra
This parameter is used for dynamic monitoring of the control valve response. The actual
position course is compared with the expected position course for this purpose. This
comparison helps in drawing a conclusion about the correct operational response of the
control valve.
Monitoring Time for Regulating Set point
This parameter is used to define the attenuation effect.
The current value is displayed in the "Control valve deviation" in Values and Counters under
Counter Thresholds and Trends. The device triggers a fault message if the current value
exceeds one of the three configurable limit thresholds.
•
Auto - Factory default
This sub-parameter is set to "Auto" if the device is auto calibrated. The time constant is
determined from the calibration process by actuating times open & close or value defined in
the velocity parameter.
•
Custom
If the time constant is inadequate, it can be change manually using this parameter. The unit
is in seconds. The value can be set from 1 to 400 seconds
Threshold Limit 1
This parameter defines the magnitude of the permissible deviation from the expected position.
•
Off
This parameter value does not trigger any message or alarm.
•
Custom
The threshold 1 fault message is displayed when the limit threshold 1 is exceeded. The value
can be set from 0.1 to 100.0%
Threshold Limit 2
This parameter defines the magnitude of the permissible deviation from the expected position.
•
Off
This parameter value does not trigger any message or alarm.
•
Custom
Summary of Contents for Posidapt Expert
Page 7: ...RTX IOM PRODUCT YY Page 7 of 131 www rotexautomation com 1 2 Posidapt Series...
Page 17: ...RTX IOM PRODUCT YY Page 17 of 131 www rotexautomation com 4 Bock Diagram...
Page 18: ...RTX IOM PRODUCT YY Page 18 of 131 www rotexautomation com 5 Dimensional Drawing...
Page 44: ...RTX IOM PRODUCT YY Page 44 of 131 www rotexautomation com 7 Electrical Connection...
Page 46: ...RTX IOM PRODUCT YY Page 46 of 131 www rotexautomation com...
Page 79: ...RTX IOM PRODUCT YY Page 79 of 131 www rotexautomation com...
Page 122: ...RTX IOM PRODUCT YY Page 122 of 131 www rotexautomation com...