This sub-parameter value is used to monitor the upper limit temperature. Set the threshold in
a range from "- 60.0 °C" to "130.0 °C" or "- 76.0 °F" to "266.0 °F".
Low Pressure Monitoring
Applicable for Posidapt
–Super and Ultra
This parameter is used to continuously monitor the minimum value of supply pressure
recorded. The current inlet pressure is recorded by a pressure sensor on the main circuit
board.
The minimum recorded value is displayed in the “Minimum pressure recorded” diagnostics
parameter. The device triggers a fault message if the current value undershoots one of the
three configurable limit thresholds.
Threshold Limit 1
This parameter is used to set the pressure threshold 1. The device triggers a fault message
if the current inlet pressure undershoots threshold 1.
•
Off
This parameter value does not trigger any message or alarm.
•
Custom
This sub-parameter value is used to monitor the lower limit pressure. Set the threshold in a
range from "0.0" to "10.0" bar.
Threshold Limit 2
This parameter is used to set the pressure threshold 2. The device triggers a fault message
if the current inlet pressure undershoots threshold 2.
•
Off
This parameter value does not trigger any message or alarm.
•
Custom
This sub-parameter value is used to monitor the lower limit pressure. Set the threshold in a
range from "0.0" to "10.0" bar.
Summary of Contents for Posidapt Expert
Page 7: ...RTX IOM PRODUCT YY Page 7 of 131 www rotexautomation com 1 2 Posidapt Series...
Page 17: ...RTX IOM PRODUCT YY Page 17 of 131 www rotexautomation com 4 Bock Diagram...
Page 18: ...RTX IOM PRODUCT YY Page 18 of 131 www rotexautomation com 5 Dimensional Drawing...
Page 44: ...RTX IOM PRODUCT YY Page 44 of 131 www rotexautomation com 7 Electrical Connection...
Page 46: ...RTX IOM PRODUCT YY Page 46 of 131 www rotexautomation com...
Page 79: ...RTX IOM PRODUCT YY Page 79 of 131 www rotexautomation com...
Page 122: ...RTX IOM PRODUCT YY Page 122 of 131 www rotexautomation com...