SuperGuard and Piguard Plus
|
1.09
10.8 Fan Air Capacity
In this screen set the fan air capacity for the, exhaust, tunnel, and variable speed fans.
Fan M3/H #01
Fan 1 30000
Fan 2 30000
Fan 3 30000
Fan 4 30000
Var.Fan 1 20000
Var.Fan 2 20000
•
Default capacity: 30000 M3/H
o
Range: 0 – 99999
•
Default capacity unit: M3/H
o
Variable: M3/H or CFM
•
Default weight value: KG; Options: KG or LB
•
Default temperature unit: Celsius; Options: Celsius or Fahrenheit
NOTE:
To select the capacity unit, weight value, and temperature unit refer to SuperGuard Setup,
page 18.