5 CONTROL MENU
•
•
•
•
•
•
5.1 Temp Curve
TEMP CURVE #01
#
Day
Target
Heat Tunnel Low Alarm High Alarm
1
1
74.0
70.0
99.0
70
99.0
2
14
72.0
68.0
99.0
50.0
99.0
3
42
70.0
66.0
90.0
50.0
95.0
4
70
69.0
64.0
85.0
50.0
95.0
5
98
68.0
62.0
80.0
50.0
90.0
..10
PIGUARD provides separate temperature curves for growth day, target temperature, heat temperature,
tunnel temperature and low/high alarm temperatures. The controller creates a curve for each one and
uses it as a reference. The program alters at midnight prior to the next day on the next row
programmed. There are up to 10 programmable rows, but the controller maintains yesterday’s settings
for every empty line; therefore it is not necessary to fill the entire table.
Limits:
•
Day: 0 - 999
•
Target: 0 - 40° C
•
Alarm low: 0 - 40° C (without floating point)
•
Alarm high: 0 - 40° C (without floating point)
5.2 Min. Max. Level
The Minimum/Maximum Level menu sets the current absolute minimum and maximum ventilation levels
available. There are five minimum/maximum level choices:
•
Min/Max by Growth Day
•
Soft Min/Max by Day
•
Min/Max by Time of Day
•
Soft Min/Max by Time
•
Cold/Warm (refer to Setting Cold Warm Levels, page 22)
•
By Weight (refer to By Weight, page 23)