September 2016
6
Quick Start Guide
2.5 Bolting considerations
If the transmitter installation requires assembly of a process flange, manifold, or
flange adapters, follow these assembly guidelines to ensure a tight seal for
optimal performance characteristics of the transmitter. Only use bolts supplied
with the transmitter or sold by Emerson Process Management as spare parts.
Figure 4 on page 6
illustrates common transmitter assemblies with the bolt
length required for proper transmitter assembly.
Figure 4. Common Transmitter Assemblies
A. Transmitter with coplanar flange
B. Transmitter with coplanar flange and optional flange adapters
C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional Rosemount Conventional Manifold and
flange adapters
Note
For all other manifolds, contact Customer Central technical support.
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing
the markings on the head of the bolt and referencing
Table 1
. If bolt material is
not shown in
Table 1
, contact the local Emerson Process Management
representative for more information.
Use the following bolt installation procedure:
1. Carbon steel bolts do not require lubrication and the stainless steel bolts are
coated with a lubricant to ease installation. However, no additional lubricant
should be applied when installing either type of bolt.
4
⫻
1.75-in. (44 mm)
4
⫻
2.88-in. (73 mm)
A
B
C
4
⫻
1.75-in. (44 mm)
D
4
⫻
1.50-in. (38 mm)
4
⫻
2.25-in. (57 mm)
4
⫻
1.75-in. (44 mm)
Summary of Contents for 4088A MultiVariable