Quick Start Guide
21
September 2016
Canada
All CSA hazardous approved transmitters are dual seal certified per ANSI/ISA
12.27.01–2003.
E6
CSA Explosionproof, Dust-Ignitionproof, and Division 2
Certificate: 2618446
Standards: CSA C22.2 No. 0-10, CSA C22.2 No. 25-1966, CSA C22.2 No. 30-M1986,
CSA C22.2 No. 94-M91, CSA C22.2 No. 142-M1987,
CSA C22.2 No. 213-M1987, CSA C22.2 No. 60079-0:2011,
CSA C22.2 No. 60079-11:2011, ANSI/ISA 12.27.01-2003
Markings: Class I, Division 1, Groups B, C, D; Class II, Division 1, Groups E, F, G; Class III;
Class I, Division 2, Groups A, B, C, D; Temp Code T5; seal not required; when
installed per Rosemount Drawing 04088-1053; Type 4X
I6
CSA Intrinsically Safe
Certificate: 2618446
Standards: CSA C22.2 No. 0-10, CSA C22.2 No. 25-1966, CSA C22.2 No. 30-M1986,
CSA C22.2 No. 94-M91, CSA C22.2 No. 142-M1987, CSA C22.2 No. 157-92,
CSA C22.2 No. 213-M1987, CSA C22.2 No. 60079-0:2011,
CSA C22.2 No. 60079-11:2011, ANSI/ISA 12.27.01-2003
Markings: Class I, Division 1, Groups C, D, Temp Code T3C; Class I Zone 0 Ex ia IIB T4;
when installed per Rosemount Drawing 04088-1207; Type 4X
Europe
E1
ATEX Flameproof
Certificate: FM12ATEX0030X
Standards: EN 60079-0:2012, EN 60079-1:2007, EN 60079-26:2008,
EN 60529:1991+A1:2000
Markings:
II 1/2 G Ex d IIC T6…T4, T4/T5 T
a
=-50 °C to 80 °C,
T6 Ta=-50 °C to 65 °C, Ga/Gb
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take
into account the environmental conditions to which the diaphragm will be subjected.
The manufacturer's instruction for maintenance shall be followed in detail to assure
safety during its expected lifetime.
2. In case of repair, contact the manufacturer for information on the dimensions of the
flameproof joint.
3. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C
greater than the maximum specified temperature for location where installed.
4. The applicable temperature class, ambient temperature range and process temperature
range of the equipment is as follows:
T4 for –50 °C
≤
T
a
≤
80 °C with T process = –50 °C to 120 °C
T5 for –50 °C
≤
T
a
≤
80 °C with T process = –50 °C to 80 °C
T6 for –50 °C
≤
T
a
≤
65 °C with T process = –50 °C to 65 °C
5. The Transmitter can be installed in the boundary wall between an area of Category 1
and Category 2. In this configuration, the process connection is installed in Category 1,
while the transmitter housing is installed in Category 2.