8.0 Product certifications
Rev 1.3
8.1 European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick
Start Guide. The most recent revision of the EU Declaration of Conformity can be
found at
EmersonProcess.com/Rosemount
.
8.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the
design meets the basic electrical, mechanical, and fire protection requirements
by a nationally recognized test laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
8.3 Installing Equipment in North America
The US National Electrical Code (NEC) and the Canadian Electrical Code (CEC)
permit the use of Division marked equipment in Zones and Zone marked
equipment in Divisions. The markings must be suitable for the area classification,
gas, and temperature class. This information is clearly defined in the respective
codes.
USA
E5
FM Explosionproof (XP), Dust-Ignitionproof (DIP) and Nonincendive (NI)
Certificate: 3045445 / 3052850
Standards: FM Class 3600 - 2011, FM Class 3611 - 2004, FM Class 3615 - 2005,
FM Class 3616 2011, FM 3810 - 2005, ANSI/NEMA 250 - 1991,
ANSI/IEC 60529 - 2004
Markings: XP Class I, Division 1, Groups B, C, D (Ta = -50 °C to 85 °C);
DIP Class II and Class III, Division 1, Groups E, F, G (T
a
= -50 °C to 85 °C);
Class I Zone 0/1 AEx d IIC T5 (T
a
= -50 °C to 80 °C);
Nonincendive Class I, Division 2, Groups A, B, C, D; T4(-50 °C
≤
T
a
≤
70 °C);
enclosure Type 4X/IP66/IP68; conduit seal not required
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local,
national, and international standards, codes, and practices. Review this document for any restrictions
associated with a safe installation.
Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the loop
are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is
applied to the unit.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a 1/2-14 NPT thread form.
Entries marked "M20" are M20
⫻
1.5 thread form. On devices with multiple conduit entries, all entries
will have the same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread
form when closing these entries.
When installing in a hazardous location, use only appropriately listed or Ex certified plugs, adapters, or
glands in cable/conduit entries.