Device functions
Version 1
RES-5006
Page 53
Part 3 of 3: Error messages (warnings)
NOTE:
The specified error messages are first output as warnings (actual value output switches between two
values; alarm LED flashes; alarm relay is not active). After the START signal is activated, it is output as a mal-
function (actual value output no longer changes, see bold-italic values; alarm LED is permanently lit; alarm relay
is active).
Error no.
Actual
value
output
Voltage
[V]
Cause
Measure if initial start-
up
Measure if machine in
operation, heating ele-
ment not changed
10
111
6.66
10
Current signal incorrect,
Calibration not possible
Error range
,
Check configuration
Error ranges
(“Loose connection”)
11
112
7.33
10
Voltage signal incorrect,
Calibration not possible
Error range
,
Check configuration
Error ranges
(“Loose connection”)
12
113
8.00
10
Voltage/current signal incor-
rect,
Calibration not possible
Error ranges
,
Check configuration
Error ranges
(“Loose connection”)
13
114
8.66
10
Temperature fluctuates,
Calibration not possible
Perform
AUTOCAL
and/or
Error ranges
(“Loose connection”)
Perform
AUTOCAL
and/or
Error ranges
(“Loose connection”)
115
Ext. calibration temperature
too large,
Calibration not possible
Perform
AUTOCAL
with
ext. calibration tempera-
ture ≤40 °C
Perform
AUTOCAL
with
ext. calibration tempera-
ture ≤40 °C
116
Ext. calibration temperature
fluctuates,
Calibration not possible
Perform
AUTOCAL
with
stable ext. calibration
temperature
Perform
AUTOCAL
with
stable ext. calibration
temperature