Accura 2350-TEMP User Guide
Chapter 3 Accura 2350-TEMP Operation/Setup
ⓒ
2020 Rootech Inc. All Rights Reserved
Page 23
Event Alarms
The Accura 2350-TEMP module gives users event alarms with its LCD backlight and EVENT LED. In
addition, if users enable the event buzzer, warning sound comes out of the device when an event occurs.
When the Digital Output is enabled, event alarms are provided via the DO. If the polarity of the DO is
set to Normal(the contact point is usually open), event alarms are offered via the DO in the status where
the contact point gets closed. If the polarity of the DO is set to Reverse(the contact point is usually
closed), event alarms are offered via the DO in the status where the contact point gets open.
Event Reset
Users can reset events on external temperature with the RESET button at the back of the Accura 2350-
TEMP module. Users can also reset events with the Digital Input and the EVENT button on the Accura
2350-TEMP module. Those buttons are originally deactivated. Thus, in order to use the features, users
should activate them via the
EVENT SETUP
>
EVENT RESET
menu in
SETUP mode. For events on the
Accura TSEN module, users can reset events only with the RESET button on the device. Users can check
detailed data on temperature events with the EVENT button on the front of the Accura 2300S device,
but cannot reset event alarms.
Fig 3.2 Event Alarms and Reset
DIO Events
Event Occurrence
Digital Input/Output events include DI and DO events. DI and DO events can be recorded in the event
logs. However, there is no event alarm for DI and DO events. Users can check data on the contact point
status and occurrence time of DI and DO events by entering the event mode on the LCD screen.