Accura 2350-TEMP User Guide
Chapter 2 Accura TSEN Operation/Setup
ⓒ
2020 Rootech Inc. All Rights Reserved
Page 17
Item
Description
Communication ID
1
–
5
Standby ID
0 (Factory default ID number, communication unavailable)
RESET Button
Users can reset event alarms settings with the RESET Button on Accura TSEN.
Communication
Item
Description
Port name
RJ45A, RJ45B (RJ45A and RJ45B ports have the same functions)
Connector type
RJ45
Protocol
RS-485 based internal dedicated protocol
Communication cable
Ethernet cable CAT.5e FTP(F/UTP)
1
Communication cable length
Up to 25m
1. FTP(F/UTP): Foiled Shield Twisted Pair
LED Status Indicators
In normal operation, the LED on the Accura TSEN device blinks green. When an event occurs, it blinks
red. Users can reset event alarms settings with the RESET Button at the top of the Accura TSEN device.
LED Color
Description
Green
Blinks green in normal operation mode .
Red
Blinks red when the measured temperature exceeds the threshold and a start event occurs.
Temperature Measurement
Item
Description
Temperature sensor
STS21 (located at the bottom end of the device)
Sensirion’s CMOS sensor technology
Accuracy error
typ.
1.0
℃
Temperature
measuring range
-20
−
100
℃
Response time
[
τ
63%]
Maximum 30 seconds
Summary of Contents for ACUURA 2350-TEMP
Page 1: ......