Page 45
‡
Class 0.5S means IEC62053-22 Class 0.5S.
1
Power and power factor values appear as zero if the voltage or current value is less than the
pickup value.
True RMS Accuracy
Harmonic
Accura 3300
Voltage
Current
5
th
±
1.0%
±
1.0%
7
th
±
1.0%
±
1.0%
11
st
±
1.0%
±
1.0%
13
rd
±
1.0%
±
1.0%
25
th
±
1.0%
±
1.0%
31
st
±
1.0%
±
1.0%
*Voltage : 220V, Tested percentages of harmonic-to-fundamental: 50%
Current : 5A, Tested percentages of harmonic-to-fundamental: 50%
Reliability Test
IEC 61326, Electrical Equipment for Measurement, Control, and Laboratory Use- EMC
Standard
Limit
Accura 3300
IEC 61000-4-2
Electrostatic Discharge[ESD]
4kV/8kV contact/air
12kV/20kV
IEC 61000-4-3
EM Field
10V/m
10V/m
IEC 61000-4-4
Electric Fast Transient
2kV
4kV
IEC 61000-4-5
Surge Immunity
1kV/2kV, line to line/line to
earth
4kV/2kV
IEC 61000-4-6
Conducted RF Immunity
3V
3V
IEC 61000-4-8
Rated Power Frequency Magnetic Field
30A/m
30A/m
IEC 61000-4-11
Voltage Dip/Short Interruptions
0.5 cycles, each polarity 100%
0.5 cycles, each polarity 100%