Page 15
Chapter 2 Mounting
Installation Conditions
The Accura 3300 should be mounted in a dry, dirt free location away from heat sources and high
electric fields. To operate the product properly and effectively, the environmental conditions below
should be considered.
Environmental Conditions
Description
Installation location
Indoors
Operating Temp
-20 to 70
C[-4 to 158
℉
]
Storage Temp
-40 to 85
C[-40 to 185
℉
]
Operating Humidity
5 - 95% (non-condensing)
Caution
The meter should be installed in a switchgear cabinet or similar enclosure to ensure the terminal
strips on the meter base are not user accessible after installation.
Mount the meter in a dry location free from dirt and corrosive vapors. Once installed, no cleaning
of the device is necessary.