Page 28
Step 4: Wiring the Power Supply and Ground Terminal
Fig 1.19 Wiring of Power Supply and Ground Terminal
Power Supply
Item
Description
Pin name
PP[+/L], PN[-/N]
Connector
Screw terminal[Pluggable]
Wire
1.25 to 3.5 mm
2
[ 24 to 14 AWG]
Ratings
AC 85 - 265V, 50/60Hz -, DC 100 - 300V
Compliance
Pollution degree 2
Burden
10VA
Caution
Using DC voltage is recommended for power supply to keep operating meters during a power
failure.
Ground Terminal
Item
Description
Pin name
G
Connector
Screw Terminal[Pluggable]
Wire spec
2.1 to 3.5 mm
2
[ 14 to 12 AWG]