Event Reset
It indicates how to reset event notification settings. Users can reset notification settings for external
temperature events on the Accura 2350-TEMP module using the RESET button on the back of the
module or the Digital Input and the EVENT button.
Caution
For events on the Accura TSEN device, users can reset notification settings only with the RESET button
on the device. Users can check detailed data on temperature events with the EVENT button on the
front of the Accura 2300[S] device but cannot reset event notification settings.
Screen
Setup Item
Range
Default
DI
- Disable : the reset function is disabled
- Event LED: the function to reset the Event
LED is enabled.
- DO: the function to reset the DO is enabled.
- Both: the function to reset the Event LED and
DO is enabled
Disable
EVENT Btn
1
- Disable : the reset function is disabled
- Event LED: the function to reset the Event
LED is enabled
- DO: the function to reset the DO is enabled.
- Both: the function to reset the Event LED and
DO is enabled
Disable
1. If users activate the selected setup item and long press the EVENT button on the Accura 2350-TEMP module,
alarms on the selected event are reset.
DIO Setup
It indicates the setup for Digital Inputs (DI) and Digital Outputs (DO).
DI
Screen
Setup Item
Range
Default
Polarity
Polarity of the logic value for the contact point
of the DI
- Normal mode
0: Open contact 1: Closed contact
- Reverse mode
0: Closed contact 1: Open contact
Normal