Chapter 2 Accura TSEN Operation/Setup
Accura 2350-TEMP User Guide
Page 18
ⓒ
2020 Rootech Inc. All Rights Reserved
Item
Description
Communication ID
1
–
6
Standby ID
0 (Factory default ID number, communication unavailable)
RESET Button
Users can reset event alarms with the RESET button on Accura TSEN.
Communication
Item
Description
Port name
RJ45A, RJ45B (RJ45A and RJ45B ports have the same functions.)
Connector type
RJ45
Protocol
RS-485 based internal protocol
Communication cable
Ethernet cable 24 AWG Solid Copper CAT.5e FTP(F/UTP)
1
Communication cable length
Up to 25 m
1. FTP(F/UTP): Foiled Shield Twisted Pair
LED Status Indicators
In normal operation, the LED on the Accura TSEN device blinks green. When an event occurs, it blinks
red. Users can reset event alarms with the RESET button at the top of the Accura TSEN device.
LED Color
Description
Green
Blinks green in normal operation mode .
Red
Blinks red when the measured temperature exceeds the threshold value and an event
occurs.
Temperature Measurement
Item
Description
Temperature sensor
CMOS sensor (located at the front bottom of the device)
Accuracy
Typ.
1.0
℃
Measurement cycle
1 second
Measuring range
-20 to
100
℃
Response time[
τ
63%]
Maximum 30 seconds
Summary of Contents for Accura 2350-TEMP
Page 1: ......