Appendix A Specifications
Accura 2350-DCM User Guide
Page 38
ⓒ
2018 Rootech Inc. All Rights Reserved
of RJ12-1 and RJ12-2 ports).
4. Over/Under events are detected by monitoring the voltage/current data aggregated over 20 ms intervals.
5. Data aggregated over 1 second is also provided. Refer to the aggregation section of Accura 2300[S] User Guide for
details.
6. The minimum DC voltage for the stand-alone operation of the DCM-50V module is 12V, and a value below 12V is not
measured.
7. The measured value below the configured minimum measured value is processed as zero.
8. Measured current values may involve errors as the temperature changes based on the calibration temperature.
9. An Over event occurs when the measured value exceeds the threshold and is maintained during the delay time.
10. An Under event occurs when the measured value exceeds threshold and is above or equal to the threshold 2, and
the value is maintained during the delay time.
11. The operations of different digital outputs are as follows.
Output Type
Command Value Operation
13, 14
Latch
1
Closed contact is maintained.
0
Open contact is maintained.
Periodic Pulse
1
Pulses occur periodically on the closed contact.
0
After completion of the pulse in progress, pulse generation
is stopped.
Uncountable Pulse 1
A single pulse occurs on the closed contact. The command
issued after the occurrence of a single pulse is cleared
automatically. Additional commands issued within the
pulse period are ignored.
0
It is unavailable because the command is automatically
cleared after pulse generation.
Countable Pulse
15
1
A single pulse occurs on the closed contact. The command
issued after the occurrence of a single pulse is cleared
automatically. Additional commands issued within the
pulse period are counted and the counted number of
pulses occur after the end of the pulse period.
0
It is unavailable because the command is automatically
cleared after pulse generation.
12. A pulse features the pulse period and pulse on time.
13. It applies when the output polarity is "normal". If the output polarity is "reversed", the operation of the contact
is reversed.
14. If DO channels are configured to operate when an event occurs, DO signals are generated, and DO signals are
cleared by long pressing the SET button.
15. It is supported via commands issued only by communication, and uncountable pulses are output when the
device’s
DO channels are configured to operate when an event occurs.
16. Compliant with the UL61010-1 standard(3rd edition)
.