Appendix A Specifications
Accura 2350-DCM User Guide
Page 36
ⓒ
2018 Rootech Inc. All Rights Reserved
Appendix A Specifications
Item
Description
Voltage Connection Terminal
Terminal name
1
Source(S) +, - / Load(L) +, -
Connector type
Bus bar type
Voltage range
DC 12
–
55 V
Accura 2350-DCM-50V Stand-alone operation
DC 0
–
55 V
Accura 2350-DCM-50V Linked operation
DC 0
–
550 V
Accura 2350-DCM-500V Linked operation
Internal bus bar
12 x 3 mm
SEMS Bolt M5 x 10
Control Power Supply
Power
Receives power from Accura 2300[S] via the RJ12 communication line
Bus bar
2
DC 12
–
55 V
Accura 2350-DCM-50V Stand-alone operation
Power consumption
125 mA when connected to Accura 2300[S] via the RJ12 communication line
3
40 mA @ DC 12 V bus bar
Accura 2350-DCM-50V Stand-alone operation
12 mA @ DC 48 V bus bar
Voltage Measurement
Sampling time
1 ms
Aggregation of
measurement data
Aggregates data for 20 ms
4
based
on the data measured over 1 ms
Window aggregation: 1
–
32 ms
(default: 20 ms)
Aggregates data for 0.5 seconds
5
based on the data measured over 20 ms
Accuracy
±
0.5% RD
±
0.03% FS
Accura 2350-DCM-50V
FS=50V
Accura 2350-DCM-500V
FS=500V
Measuring range
[accuracy guaranteed]
6
DC 3
–
50 V
Accura 2350-DCM-50V
DC 30
–
500 V
Accura 2350-DCM-500V
Minimum measured value
6,
7
DC 0.2 V
Accura 2350-DCM-50V
configurable
DC 2 V
Accura 2350-DCM-500V
Maximum measured value
DC 55 V
Accura 2350-DCM-50V
DC 550 V
Accura 2350-DCM-500V
Current Measurement
Sampling time
1 ms
Aggregation of
Aggregates data for 20 ms
4
based
on the data measured over 1 ms
Aggregation
window: 1
–
32 ms (default 20 ms)
measurement data
Aggregates data for 0.5 seconds
5
based on the data measured over 20 ms
Accuracy
±
0.5% RD +
±
0.06% FS
FS=80A
Measuring range
[accuracy guaranteed]
DC 0.8
–
80 A
Minimum measured value
7
DC 0.08 A
Configurable
Summary of Contents for ACCURA 2350-DCM
Page 1: ......