R 6
(
*
)
Value Dec Sending a command to the module
By means of this register, functions like the reset of counters,
masks or even the entire module can be triggered by sending a
command to the device.
1
Resets the module via watchdog (incl. reset of all masks to
default values!)
30
Resets all counter values to zero
255
Resets all EEPROM parameters to default
285
= commands 30 + 255
R 1
(
*
)
Value Dec Reading the set bus address
With this register the adjusted address of the module can be
read via the bus.
R 10
(
*
)
Value Dec Reading the type of module
This register contains the type of module in a coded form. The
values have the following meaning:
15116
romod 16 DI eco
15008
romod 8 DO eco
15508
romod 8 DO-R eco
15504
romod 4 DIO-R eco
15404
romod 4 DO-R eco
15308
romod 8 AI eco
15208
romod 8 AO eco
R 12
(
*
)
Value Dec Reading the firmware version
Using this register, the firmware version of the module can be
read via the bus.
R 22
(
*
)
Value Dec Reading the current baud rate
By means of this register, the baud rate with which the module is
currently communicating can be read. Doing so, it does not
matter whether the baud rate has been fixed using the registers
R2 and R3, or it has been identified by the autobaud function.
1
… 4
Meaning of the values identical to register R2