Rev 20.11.2019
V1.07 - Page 42
Subject to modifications!
romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald
www.romutec.de
Subject to technical changes
R2121
Value Hex Defining the DO's states for the 'Safe State' mode
DO No.
(DO4 .. DO1) In this register, the states are defined which shall apply for the
outputs in case of a failure of the MODBus. The prior condition
is that the corresponding bits in register R 2135 are set to 1.
Each digital output is assigned to a bit of the register. The
assignment corresponds to that of the register R121 (Controlling
the DOs via bus command). The settings of this register are
stored in non-volatile memory.
00 00
All DOs will be switched OFF if safe state is triggered
1
00 01
DO 1 will be switched ON when safe state is triggered
…
…
…
4
00 08
DO 4 will be switched ON when safe state is triggered