ROLA-CHEM Digital Controller                                        PN 554135      5/04/2017                                                   Page: 17 of 20 

8.  Appendix

 

8.1   Dip switch settings 

The controller has dip switches to control functions/options that are not accessible on the front panel. These 
dip switches are located inside the power panel access cover. See section 4.3. To avoid overfeed conditions 
the Consecutive Feed Alert Limit (switch #2) should remain in the ON position. *Factory settings are 
underlined below. 
 

Control Switch 

Description 

ORP/pH interlock 

 

  

#1 OFF 

ORP chemical feeding is independent of pH feeding and range. 

  

#1 ON 
 

ORP chemical feed only when pH is within limits.  
ORP will not feed when pH chemical is feeding. 

Consecutive Feed Alert Limit -Timed feed mode (Feed time set to a value other than “con” or “off” on Controller 
front panel) 

  

#2 OFF 

There is no consecutive feed limit. 

  

#2 ON 
 

The pH & ORP chemical feeder outputs go through a preset number of 
consecutive feed cycles before feeders are disabled.  If preset count is 
reached for either pH or ORP, the respective feeder outputs will be disabled 
and its display will flash indicating a Consecutive Feed Alert. 

  

 

The number of consecutive feed cycles on model RC554XP is 20 to 100 
(default is 20) and can be independently set for both pH and ORP. The range 
on 554000 is 3 to 20 (default is 10). 
Setting consecutive feed cycle limit to OFF voids NSF certification. 

  

 

 

  

  

To adjust the Consecutive Feed Alert Limit feature in the 'timed feed mode'                
1) Turn off & remove power, then move #2 dip switch to ON.                                       
2) Re-power & press MODE to set it for ORP or pH. 
3) Set FEED TIME to OFF. 
4) Press FEED ONCE to select the feed count.                   
5) Press FEED TIME and return the time to the desired cycle. 

Consecutive Feed Alert Limit -Continuous feed mode (Feed time set to 'con' on Controller front panel) 

  

#2 OFF 

There is no consecutive feed limit. 

  

#2 ON 
 

The pH & ORP chemical feeder outputs continuously feed for a preset time 
before feeders are disabled.  If the preset time period is reached for either 
pH or ORP, the respective feeder output will be disabled and its display will 
flash indicating a Consecutive Feed Alert. 

  

  

The Consecutive Feed Alert Limit period can be set from 20 to 180 minutes 
on model RC554XP (default is 20) and can be independently set for both pH 
and ORP. The range on 554000 is 10 to 99 (default is 10). 
Setting consecutive feed time limit to OFF voids NSF certification. 

  

 

 

  

  

To adjust the Consecutive Feed Alert Limit feature in the 'Continuous feed 
mode'                                                                                                      
1) Turn off & remove power, then move  #2 dip switch to ON. 
2) Re-power & press MODE to set it for ORP or pH. 
3) Set FEED TIME to ‘con’. 
4) Press FEED ONCE button to select the default feed time.  

Acid/Base pH chemical feed 

  

#3 OFF 

Unit set to feed acid chemical when pH is over set-point. 

  

#3 ON 

Unit set to feed base chemical when pH is under set-point. 

Keypad Lockout  

  

  

#4 OFF 

 

Key pad operable to set controller parameters. 

  

#4 ON 

Key pad operable only for pH calibration. Other parameters stay at settings 
established prior to moving dip switch #4. 

 

Summary of Contents for RC554000

Page 1: ...F MODE FEED ONCE pH AUTO ORP LEVEL SET pH FEED ALERT CALIB pH FEED TIME HI ORP LOW ORP FEED L O W ALERT pH Operating Manual MODELS RC554XP AND 554000 ORP pH Digital Controller IMPORTANT SAFETY INSTRUC...

Page 2: ...lso remove power from the controller Provide a properly located outlet controlled by the circulating pump circuit 1 6 WARNING Risk of electric shock pinching chemical exposure Remove power sources or...

Page 3: ...ols 7 4 Installation 4 1 Locating the controller 10 4 2 Mechanical installation 10 4 3 Power panel access 11 4 3 1 Dip switches 11 4 3 2 Fuses 11 4 3 3 Flow switch 11 5 Operation 5 1 Startup 12 5 2 pH...

Page 4: ...low pH 8 0 high 7 0 low To Change Settings Press and release the MODE button until the desired ORP or pH LED is lit Once the settings are changed they will remain at those settings until they are chan...

Page 5: ...ontinuously during the feed delay portion of the feed cycle The ORP Alert lamp will illuminate when the ORP reading is higher or lower than the high and low ORP Alert set points and prevent the feedin...

Page 6: ...ire grounded power cord Combined load not to exceed 10 amps GFCI source required Output Power 120 Volts AC 50 60 HZ 5 amps fused for both ORP and pH Two 3 wire grounded power receptacles Terminal stri...

Page 7: ...ing feed delay 4 pH ORP DIGITAL DISPLAYS Monitors pH and ORP and displays programmed set points 5 pH STANDBY LAMP AND PROGRAMMING BUTTONS When pH standby lamp is illuminated the six set buttons are en...

Page 8: ...ssing the FEED ONCE button the pH feeder will feed and delay for one complete feed cycle See FEED TIME Button for feed delay times If the Feed time is set for Continuous feed the manual feed will not...

Page 9: ...ET LEVEL button which displays in 5 mV increments until the desired level is reached Feed Time The feed times are displayed in seconds There is a five 5 minute delay time associated with each feed tim...

Page 10: ...roller in a location accessible to the public Install the controller in an area protected from natural elements sun rain freezing etc See appendix for typical feed system schematics 4 2 Mechanical Ins...

Page 11: ...dix for settings 4 3 2 Fuses The ORP and pH are independently fused to protect the controller from defective feeders These fuses are located inside the lower panel The fuse holders are shipped with 5...

Page 12: ...n the OFF mode turn the filter pump on and check for leaks in the system and flow through the flow cell The flow lamp will be illuminated if the controller has power it is connected to the flow switch...

Page 13: ...until the AUTO LED is lighted This is the operational mode for the controller The controller must be in this mode for the feeders to maintain the desired parameters Note When using the RC554XP or 5540...

Page 14: ...affected by pH probe Both probes must be in good operating condition 6 3 Set points not being reached maintained Factory setting for feed time is 0 6 sec on with 5 minute delay Feeders may require lo...

Page 15: ...and return to operating mode The last two steps are extremely important because this puts the controller back in operating mode If these two steps are not performed the controller will remain in test...

Page 16: ...are not covered under this warranty Heavy duty probes are warranted from the date of original purchase for one 1 year ROLA CHEM under no circumstances shall be liable for any consequential damages di...

Page 17: ...eed Alert Limit feature in the timed feed mode 1 Turn off remove power then move 2 dip switch to ON 2 Re power press MODE to set it for ORP or pH 3 Set FEED TIME to OFF 4 Press FEED ONCE to select the...

Page 18: ...mode shortens minutes to seconds E Turn the controller Off again to exit test mode F Turn the controller On to return to operating mode The last two steps are extremely important because this puts th...

Page 19: ...CLEAR OF DEBRIS FLOWSWITCH EARTH GROUND WATER TO POOL ACID PUMP HEATER ACID HCl MANIFOLD FLOWSWITCH VALVE EARTH GROUND WATER FROM POOL WATER TO POOL EARTH GROUND SYSTEM USING EROSION FEEDER TRI CHLOR...

Page 20: ...FROM POOL BASKET POOL PUMP FILTER CONTROLLER FLOWSWITCH CELL WATER TO POOL SPDT 120 VAC COIL RELAY COM NO NC MANIFOLD FLOWSWITCH STRAINER VALVE SAFETY FLOWSWITCH TO ENSURE CIRCULATION TO CONTROL PROB...

Reviews: