ROLA-CHEM Digital Controller                                        PN 554135      5/04/2017                                                   Page: 12 of 20 

The flow switch light on the face of the controller is also a power light that shows that the 
controller is connected to a live power source.  If the terminal does not have a closed circuit, 
the controller will not turn on. 
 
NSF certification of this automated controller requires the use of a flow switch.  To install a 
flow switch, remove the jumper and install the flow switch leads. Note: With the flow switch 
installed and the jumper removed, the flow light will no longer operate as a power light. It is 
recommended the jumper be retained to assist in troubleshooting if necessary. 
 

Note: It is recommended that an inline filter be used to help keep the  
Globe Flowcell (including probes) and flow switch free from debris (see Globe Flowcell 
Operating Manual). Debris may cause obstruction in flow switch and prevent the 
switch from functioning.   
 

5.  Operation 

 

5.1 Startup  

 
Do not add chemicals to the feeders until all 

startup operations are completed. Using a DPD 

test kit, manually adjust and balance the pool to acceptable ranges. Automation should be 
used to maintain chemical levels, not to balance a pool that is far out of acceptable ranges. 
With the controller in the OFF mode, turn the filter pump on and check for leaks in the 
system and flow through the flow cell. The flow lamp will be illuminated if the controller has 
power, it is connected to the flow switch and there is adequate flow. If a flow switch is not 
attached, the flow lamp will be illuminated if there is a jumper in the flow cell connection 
allowing the controller to be used without a flow switch. Using a flow switch is always 
recommended. 
 

5.2 pH settings

   

 
Press and release the controller MODE button until the pH LED is lighted (refer to the 
description of controls). Then select the desired set level, feed time cycle and upper and 
lower alert levels. 
 

 

Note: Controller can be set to feed acid or base. See Acid/Base pH chemical feed section 
in Appendix for Dip switch settings. To verify that acid feed mode is selected adjust the pH 
set level below the pH indicated on the display. The feed lamp should come on if the 
controller is in acid feed mode. To verify that base mode is selected adjust the pH set level 
above the pH indicated on the display. The feed lamp should come on if the controller is in 
base feed mode. 

 

5.3 pH Calibration 

 
The pH sensor can drift slightly over time and calibration will offset this drift. Always calibrate 
using water from the sample port of the flow cell and use an independent pH test method to 
determine pH value of sample, unless using preset buffer solution. Press and release the 

Summary of Contents for RC554000

Page 1: ...F MODE FEED ONCE pH AUTO ORP LEVEL SET pH FEED ALERT CALIB pH FEED TIME HI ORP LOW ORP FEED L O W ALERT pH Operating Manual MODELS RC554XP AND 554000 ORP pH Digital Controller IMPORTANT SAFETY INSTRUC...

Page 2: ...lso remove power from the controller Provide a properly located outlet controlled by the circulating pump circuit 1 6 WARNING Risk of electric shock pinching chemical exposure Remove power sources or...

Page 3: ...ols 7 4 Installation 4 1 Locating the controller 10 4 2 Mechanical installation 10 4 3 Power panel access 11 4 3 1 Dip switches 11 4 3 2 Fuses 11 4 3 3 Flow switch 11 5 Operation 5 1 Startup 12 5 2 pH...

Page 4: ...low pH 8 0 high 7 0 low To Change Settings Press and release the MODE button until the desired ORP or pH LED is lit Once the settings are changed they will remain at those settings until they are chan...

Page 5: ...ontinuously during the feed delay portion of the feed cycle The ORP Alert lamp will illuminate when the ORP reading is higher or lower than the high and low ORP Alert set points and prevent the feedin...

Page 6: ...ire grounded power cord Combined load not to exceed 10 amps GFCI source required Output Power 120 Volts AC 50 60 HZ 5 amps fused for both ORP and pH Two 3 wire grounded power receptacles Terminal stri...

Page 7: ...ing feed delay 4 pH ORP DIGITAL DISPLAYS Monitors pH and ORP and displays programmed set points 5 pH STANDBY LAMP AND PROGRAMMING BUTTONS When pH standby lamp is illuminated the six set buttons are en...

Page 8: ...ssing the FEED ONCE button the pH feeder will feed and delay for one complete feed cycle See FEED TIME Button for feed delay times If the Feed time is set for Continuous feed the manual feed will not...

Page 9: ...ET LEVEL button which displays in 5 mV increments until the desired level is reached Feed Time The feed times are displayed in seconds There is a five 5 minute delay time associated with each feed tim...

Page 10: ...roller in a location accessible to the public Install the controller in an area protected from natural elements sun rain freezing etc See appendix for typical feed system schematics 4 2 Mechanical Ins...

Page 11: ...dix for settings 4 3 2 Fuses The ORP and pH are independently fused to protect the controller from defective feeders These fuses are located inside the lower panel The fuse holders are shipped with 5...

Page 12: ...n the OFF mode turn the filter pump on and check for leaks in the system and flow through the flow cell The flow lamp will be illuminated if the controller has power it is connected to the flow switch...

Page 13: ...until the AUTO LED is lighted This is the operational mode for the controller The controller must be in this mode for the feeders to maintain the desired parameters Note When using the RC554XP or 5540...

Page 14: ...affected by pH probe Both probes must be in good operating condition 6 3 Set points not being reached maintained Factory setting for feed time is 0 6 sec on with 5 minute delay Feeders may require lo...

Page 15: ...and return to operating mode The last two steps are extremely important because this puts the controller back in operating mode If these two steps are not performed the controller will remain in test...

Page 16: ...are not covered under this warranty Heavy duty probes are warranted from the date of original purchase for one 1 year ROLA CHEM under no circumstances shall be liable for any consequential damages di...

Page 17: ...eed Alert Limit feature in the timed feed mode 1 Turn off remove power then move 2 dip switch to ON 2 Re power press MODE to set it for ORP or pH 3 Set FEED TIME to OFF 4 Press FEED ONCE to select the...

Page 18: ...mode shortens minutes to seconds E Turn the controller Off again to exit test mode F Turn the controller On to return to operating mode The last two steps are extremely important because this puts th...

Page 19: ...CLEAR OF DEBRIS FLOWSWITCH EARTH GROUND WATER TO POOL ACID PUMP HEATER ACID HCl MANIFOLD FLOWSWITCH VALVE EARTH GROUND WATER FROM POOL WATER TO POOL EARTH GROUND SYSTEM USING EROSION FEEDER TRI CHLOR...

Page 20: ...FROM POOL BASKET POOL PUMP FILTER CONTROLLER FLOWSWITCH CELL WATER TO POOL SPDT 120 VAC COIL RELAY COM NO NC MANIFOLD FLOWSWITCH STRAINER VALVE SAFETY FLOWSWITCH TO ENSURE CIRCULATION TO CONTROL PROB...

Reviews: