15
DALIS PRO
DOMESTIC HOT WATER HEAT PUMP
EN
X1
X2
X3
Y1
650 mm
650 mm
200 mm
300 m
The product
MUST NOT
be installed in locations where:
•
The air intake contains solvents, explosive matter, grease, dirt or dust / aerosol
particles.
•
It is outdoors/in rooms exposed to frost, ice or damp, or in rooms where there is a lot
of steam/vapour (e.g. a bathroom).
•
It is sat on floor slabs containing wooden beams e.g. attics, to avoid vibrations.
•
It is prohibited to connect vented exhaust hoods to ventilation systems.
8.4. Ventilation
When carrying out the installation of each air duct take care that:
•
The weight of the ducts does not adversely affect the equipment itself.
•
Maintenance operations can be carried out.
•
They are adequately protected to prevent the intrusion of material inside the equipment.
•
The maximum allowable total pressure drop for all components, including through
holes for external wall mounting, within the piping system must not exceed 77 Pa.
Fig 4a - Example of an air outlet duct
An alternative solution is indicated in Fig 4b. This consists of a second duct that draws air
in from outside instead of directly from inside the premises.