The unit is on
•
T3 (upper tank water temperature)
≤
parameter 15-2ºC
•
T6 (temperature of circulation water - thermosensor 18)
≥
parameter 15
Parameters for recirculation pump function:
Code
Description
Range
Default
Remarks
14
Type of water pump
0/1/2
0
0: no water pump 1: (circulation pump)
2: (solar water pump)
15
Setting circulation
water temperature
15~50 ºC
35ºC
Adjustable
16
Temp difference to
start the circulation
water pump
1~15 ºC
2 ºC
Adjustable
11.4. ON/OFF contact
Parameter 35, must be set to “0”.
•
When ON/OFF contact is closed, and the controller is ON, the unit can work and the
running mode is decided by the setting of the controller.
•
When ON/OFF contact is closed, but the controller is OFF, the unit can’t work.
•
When ON/OFF contact is opened, but the controller is ON, the unit can’t work (with
the exception of external pump).
•
If the controller is ON, and the ON/OFF status is changed from opened to closed, the
unit will work by the previous settings of the controller (auto-restart).
•
If the unit was previously in stand-by, in case the ON/OFF status is changed from
opened to closed, the unit remains in stand-by.
•
A signal/warning in case of remote OFF signal (opened contact) is displayed. In such
a way the customer can understand why the unit is not working.
IMPORTANT
Only qualified personnel should design and install systems ON/OFF.
11.5. Electrical heater
11.5.1. Turned ON or OFF - Condition 1:
When the unit is switched on and the Electric Heater button on the control panel has not
been switched on manually: