When forgotten, MASTER and INSTALLER codes can be restored to their default values and then
programmed again.
Please not that Memory Reset procedure requires access to the JP1 programming contact therefore assure
access to the internal space of the lock even after installation.
The code lock must be supplied form reliable power source, calculate the adequate wire gauge to guarantee
that the voltage on the SL2000 DC input will be 11.5V minimum.
Use separate pair of wires to supply door lock and SL2000 code lock.
Always add the silicon diode (e.g. 1N4007) in parallel to the door lock, note that diode must be located as
close as possible to the door lock terminals.
It is forbidden to supply the door lock directly from the DC input terminals of the code lock.
Do not attempt to use REL1 output for switching of voltages higher then 24V DC/AC.