Electronic Code Locks SL2000B v1.4 and SL200S1K v1.3 EN Rev.C.doc
2011-11-16
Strona 4 z 13
Special options
Timed Lock-Out
If this option is enabled the Sl2000 disables the keypad for 60 seconds after three
attempts of entry of the incorrect code. After this time the SL2000 re-enables the
keypad and is ready to accept new keypad’s entries. The end of 60 seconds lock-out time
is indicated by two series of two beeps (** **).
Disable USER Codes When in Armed Mode
If this option is enabled the SL2000 grants access only when it operates in Disarmed
mode. With this option active the access to the controlled door will be totally disabled
unless the SL2000 will be switched to Disarmed mode again. Thanks to this formula the
MASTER user can disable access to the room by switching the unit to the Armed mode
and vice verso, he can re-enable access to the controlled door by switching the lock to
the Disarmed mode. The SL2000 can be switched between Armed and Disarmed modes
via the MASTER code only.
Codes
The SL2000 offers three types of codes:
MASTER Code
INSTALLER Code
USER Codes
Each type of code is dedicated for individual purpose. The length of each code can be
programmed during Memory Reset procedure. The entry of each code must be followed
by the [#] key which is used to mark the end of the code.
MASTER Code
The MASTER code is used to switch the SL2000 between Armed and Disarmed modes, it
can be 4-10 digits long.
INSTALLER Code
The INSTALLER code is required to enter the Installer Programming mode, it can be 4-10
digits long.
USER Codes
These codes are used solely to trigger the Door Lock (momentary) output. Each time a
valid USER code is entered the SL2000 starts counting
C1C2
time delay and then
activates Door Lock output for time defined by the
C3C4
parameters. The USER codes
can be 2-8 digits long.
Note: If you are not going to use a door open sensor leave the Door Contact input
unconnected. Without a door open sensor the SL2000 will not signal the
Door Alarm
.
Note: When the SL2000 is in Armed mode this output remains not active (red
CLOSE
LED
lights up), it become active when lock works in Disarmed mode(green
OPEN LED
lights up).
Note: The SL2000 enables programming of maximum 55 USER codes, each of them can
be used to trigger Door Lock output.
Summary of Contents for SL2000B
Page 1: ...Roger Sp j Electronic Code Locks SL2000B v1 4 and SL2000S1K v1 3 Document version Rev C ...
Page 9: ...Electronic Code Locks SL2000B v1 4 and SL200S1K v1 3 EN Rev C doc 2011 11 16 Strona 9 z 13 ...
Page 10: ...Electronic Code Locks SL2000B v1 4 and SL200S1K v1 3 EN Rev C doc 2011 11 16 Strona 10 z 13 ...
Page 11: ...Electronic Code Locks SL2000B v1 4 and SL200S1K v1 3 EN Rev C doc 2011 11 16 Strona 11 z 13 ...