MCT12E Operating Manual 

  

05.10.2020 

 

12/14 

 

Note:  Table  5  includes  summary  of  parameters  for  all  versions  of  MCT12E  terminal.  For  instance  keypad 
settings are not available for 

–BK version of terminals i.e. terminals without keypad.  

Manual addressing 

Manual addressing can be done within memory reset procedure. 

Memory reset procedure 

Memory  reset  procedure  enables  configuration  of  RS485  address  and  resets  all  other  settings  to  factory 
default ones. 
 
Memory reset procedure: 

1.  Remove all connections from A and B lines. 
2.  Connect CLK and DTA lines. 
3.  Restart the reader (switch power supply off and on or short RST contacts for a moment). 
4.  When red LED STATUS, green LED OPEN and orange LED SYSTEM are on then disconnect CLK and 

DTA lines. 

5.  When orange LED SYSTEM is on then enter 3 digits of RS485 address in range of 100-115 with reader 

keypad or with any EM125kHz proximity card. 

6.  When the third digit is defined then the reader will restart with the new address. 

Readers  without  keypad  can  be  addressed  with  multiple  card  readings  where  the  N  number  of  readings 
emulates digit of the address. Three series of readings with any EM125kHz proximity card are necessary to 
set the address. After each series wait for two beeps and proceed with the next digit. Zero digit is emulated 
with 10 readings. 
 
Example: 
Programming of ID=101 address with card readings:  

1.  Read card 1 time and wait for two beeps. 
2.  Read card 10 times and wait for two beeps. 
3.  Read card 1 time and wait for two beeps. 
4.  Wait till reader is restarted with the new address and other default settings. 

High level configuration (VISO) 

The purpose of high level configuration is to define logical functioning of the terminal which communicates 
with  the  MC16  access  controller  and  it  depends  on  applied  scenario  of  operation. The  example  of  access 
control system configuration is given in AN006 application note which is available at 

www.roger.pl

. 

5.

 

F

IRMWARE UPDATE

 

The update requires connection  of reader to computer with RUD-1  interface (fig. 8) and starting  RogerISP 
software. The latest firmware file is available at 

www.roger.pl

. 

 
Firmware update procedure: 

1.  Connect the reader to RUD-1 interface (fig. 8) and connect the RUD-

1 to computer’s USB port. 

2.  Place jumper on FDM contacts (fig. 4). 
3.  Restart the reader (switch power supply off and on or short RST contacts for a moment). 
4.  Start RogerISP program. 
5.  Select serial port with RUD-1 interface and 

USB-RS485 Converter

 option. 

6.  Specify path to firmware file (*.hex). 
7.  Click 

Program

 and proceed according to displayed messages. 

8.  Remove jumper from FDM contacts and restart the reader. 

6.

 

S

PECIFICATION

 

Table 6. Specification 

Supply voltage 

Nominal 12VDC, min./max. range 10-15VDC 

Summary of Contents for MCT12E

Page 1: ...Roger Access Control System MCT12E Operating Manual Product version 1 1 Firmware version 1 0 4 or newer Document version Rev A...

Page 2: ...ly IO versions Power supply The terminal requires power supply voltage in range of 11 15VDC It can be supplied from MCX2D MCX4D expander of MC16 PAC KIT from MC16 access controller e g TML output or f...

Page 3: ...matching resistors terminators connected at the ends of transmitting lines are not required In most cases communication works with any cable type standard telephone cable shielded or unshielded twiste...

Page 4: ...icates access granting LED SYSTEM Orange LED indicates card reading and can signal other system functions including device malfunction Note Synchronic pulsing of LED indicators signifies lost communic...

Page 5: ...rds EM125kHz proximity cards are widely used in office buildings If it is necessary to ensure higher level of security then MIFARE card readers e g MCT12M are recommended The technical characteristics...

Page 6: ...85 bus line B CLK White Green CLK line DTA Green Yellow DTA line TMP Yellow Pink Tamper contact TMP Grey Grey Tamper contact IO1 Yellow brown IO1 output line IO2 Green brown IO2 output line REL1 NC Gr...

Page 7: ...MCT12E Operating Manual 05 10 2020 7 14 Fig 5 MCT12E installation...

Page 8: ...must be connected with any wire Device can be cleaned by means of wet cloth and mild detergent without abrasive components In particular do not clean with alcohols solvents petrol disinfectants acids...

Page 9: ...MCT device firmware version RS485 communication channel and serial port with RUD 1 interface 3 Click Connect the program will establish connection and will automatically display Configuration tab 4 En...

Page 10: ...h readers Selected input must be connected to synchronisation output of another reader When set to 0 then synchronisation is disabled Typical numbering is 1 IN1 2 IN2 and 3 IN3 Range 0 3 Default value...

Page 11: ...disabled Range 0 100 Default value 100 Input types IN1 IN2 IN3 Parameter defines the type of input line Range 1 NO 2 NC Default value 1 NO Input comments IN1 IN2 IN3 Parameter defines any text or comm...

Page 12: ...the next digit Zero digit is emulated with 10 readings Example Programming of ID 101 address with card readings 1 Read card 1 time and wait for two beeps 2 Read card 10 times and wait for two beeps 3...

Page 13: ...5 bus between controller and reader IP Code IP65 Environmental class according to EN 50133 1 Class IV outdoor general conditions temperature 25 C to 60 C relative humidity 10 to 95 no condensation Dim...

Page 14: ...ctric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste cont...

Reviews: