HRT82MF-CH Installation Guide.doc

 

2018-09-21 

 

 

4/11 

 

 

Fig. 3 Connection to controller without 12VDC power supply output 

3.2 Power supply 

HRT82MF-CH  requires  12VDC  nominal  power  supply.  The  power  must  be  connected  to  12V  and 

GND terminals. Additionally, the GND terminal is used as reference potential for the RACS CLK/DTA 
bus. HRT82MF-CH power supply can be provided by connection  to buffer power supply unit (e.g. 

PS-15DR, PS20) or connection to AUX output of HRC402DR controller (see fig. 2). Backup battery 
connected to power supply unit or directly to HRC402DR controller can be used in order to ensure 
operation in case of 230VAC power failure. 

Note:  All  devices  connected  to  the  same  RACS  CLK/DTA  bus  must  be  connected  to  common 
reference potential (GND). 

3.3 RACS CLK/DTA communication bus 

RACS CLK/DTA is the addressable bidirectional communication standard developed and applied in 
Roger controllers in order to enable their communication with peripheral devices. Addresses of all 

devices connected to CLK and DTA lines must be properly configured in range of 00..15. Standard 
unshielded  signal  cables (e.g. U/UTP cat. 5)  with maximal length of 150m can be used  for RACS 

CLK/DTA communication. 

3.4 Front panel 

HRT82MF-CH  front  panel  includes  card  holder.  At  the  holder  entry,  white  backlight  is  by  default 
switched on and it is also possible to switch green and/or red light below the holder. This additional 

backlight can be switched by HRC series controller. 

3.5 Wall mounting and installation guidelines 

HRT82MF-CH  consists  of  front  panel  and  base  which  are  factory  assembled  and  require  manual 
disassembly prior to installation according to fig. 4. 

Installation guidelines 

 

Install device on wall far from sources of heat and moisture 

 

It is recommended to install device on Ø60mm flush mounting box 

 

Front  panel  and  base  must  be  properly  oriented  in  order  to  ensure  functioning  of  tamper 
resistance. 

 

All electric connections must be made with power supply switched off 

 

Run connection wires through hole in device base and then connect wires to screw terminals 

 

If  device  and  controller  are  supplied  from  different  power  supply  units  then  it  is  necessary 
connect GND terminals of both devices 

 

Front panel can be regularly cleaned with wet cloth and mild detergent. Do not clean by means 
of abrasive materials and strong cleaners like alcohols, solvents, etc. 

Summary of Contents for HRT82MF-CH

Page 1: ...ion 1 0 2 16 or newer Hardware version 1 0 Document version Rev D 2016 ROGER sp z o o sp k All rights reserved This document is subject to the Terms of Use in their current version published at the ww...

Page 2: ...CSN reading for such cards as MIFARE Ultralight Classic Plus Desfire Additionally it allows to read configurable Mad Sector Number MAD and Sector Serial Number SSN as well as combinations of CNS and...

Page 3: ...ion diagram Fig 1 HRT82MF CH card holder Table 2 HRT82MF CH terminals Term Description Term Description 12V 12VDC power supply CLK RACS CLK DTA bus GND Ground DTA RACS CLK DTA bus IN1 not used TMP Tam...

Page 4: ...shielded signal cables e g U UTP cat 5 with maximal length of 150m can be used for RACS CLK DTA communication 3 4 Front panel HRT82MF CH front panel includes card holder At the holder entry white back...

Page 5: ...HRT82MF CH Installation Guide doc 2018 09 21 5 11 Damages resulting from improper maintenance or use are not covered by warranty Fig 4 HRT82MF CH latches and surface mounting...

Page 6: ...HRT82MF CH Installation Guide doc 2018 09 21 6 11 Fig 5 HRT82MF CH F flush mounting...

Page 7: ...place and remove jumper on RST pins or switch power supply off and on 4 Install and start RogerVDM software 5 In the opened window select device firmware version communication channel and serial port...

Page 8: ...d with any comment by installer Transmission Format RACS CLK DTA Address 0 15 Device address on RACS CLK DTA bus Default address ID 0 is required for communication with HRC controller Communication ti...

Page 9: ...D sector which defines sector with MSN For SSN this setting is disabled Block ID 0 14 Block number in the sector with MSN or SSN Key Type A B Roger Type of key used for reading MSN or SSN Key 00000000...

Page 10: ...stic indication Solution No communication with controller Green red backlight is blinking 1 Check if RACS CLK DTA bus is properly connected wires are undamaged and the bus does not exceed 150 m All de...

Page 11: ...as this may have a negative impact on the environment and health The user is obliged to deliver equipment to the designated collection points of electric and electronic waste For detailed information...

Reviews: