background image

 

 

 

The Constant Fraction Discriminators CFD8c, CFD7x, CFD4c, CFD1c and CFD1x (11.0.1701.1) 

Page 21 of 25  

   

 

Figure 3.25b: Signal traces triggered on CFD timing signal. Upper trace: input signal (as in Figure 3.24b),  

lower trace: ramp monitor outputs with 

Ramp

 switch turned on. Left picture: “pure” 

ramp

 signal  

(obtained without signal input to on 

A

in

 socket), right: with signal connected to 

A

in

 (normal operation) 

The 

ramp

 monitor output 

M

Ramp

 

allows observing the “pure” 

ramp

 signal when there is no input on 

A

in

 and the switch labelled 

Ramp

 on is set to 

on

. If the 

ramp

 signal is turned 

off

 by the switch

*

 one can observe the input signal connected to 

A

in 

at the 

monitor output 

M

Ramp

. During normal operation the input signal and the 

ramp

 signal are superimposed (“

ramp

 on”, see Figure 

3.25b right). If the 

ramp

 starts from a higher level due to the overlaid (positive) input signal it takes longer until it reaches the 

reset value. 

 

The higher the input signal at the start moment of the ramp, the longer is the delay between the CFD timing and the 

stop

 signal 

and the wider is the 

CFDx

 signal. This is indicated in Figure 3.26b. 

 

The 

ramp

 slope is about -1 V per 12 ns, giving an almost linear correspondence between pulse height and time delay, with a 

typically 10 to 20 ns offset for pulse height zero given by the minimum duration of the 

ramp

 signal.  

 

If the cable length between 

A

in

 and 

A

out

 is optimally chosen, the start of the “pure” 

ramp

 signal will appear at the same time as 

the signal maximum. To achieve this, one has to compare the relative timing of the input signal (

ramp

 off) and the start of the 

ramp

 signal in absence of an input to 

A

in

 which can be observed at the 

ramp

 monitor (see Figure 3.24b left and Figure 3.25b left 

– the scope markers are set at the same position!). As a thumb rule, the cable length between 

A

in

 and 

A

out

 will be about the 

same as the 

CFD delay

 cable length (for determining relative pulse height distributions it is not mandatory that the cable length 

is exactly set). 

 

 

Figure 3.26b: upper trace: 

CFDx

 output, middle trace: 

stop

 output (with a pulse width set by the 

Stop  

Width

 potentiometer setting), lower trace: 

ramp

 monitor, all traces triggered on the 

stop

 signal.  

The 

stop

 signal should be used if there is a spare TDC channel available 

                                                           

*

 Note that the 

CFDx

 output is turned off while the 

ramp

 switch is turned off 

Summary of Contents for CFD1c

Page 1: ...Dek Handels GmbH Supersonic Gas Jets Detection Techniques Data Acquisition Systems Multifragment Imaging Systems The RoentDek Constant Fraction Discriminators CFD8c CFD7x CFD4c CFD1c and CFD1x 11 0 17...

Page 2: ...Kernphysik Max von Laue Str 1 D 60438 Frankfurt am Main Germany Web Site www roentdek com WEEE DE48573152 Product names used in this publication are for identification purposes only and may be tradema...

Page 3: ...3 CFD fraction 12 3b 3 4 Walk level 13 3b 3 5 Output signal width 14 3B 4 THE VETO OPTION 14 3b 4 1 Accessing the jumpers in CFD1c CFD1x 16 3b 4 2 Accessing the jumpers in CFD8c and CFD7x 16 3b 4 3 A...

Page 4: ...Page 4 of 25 The Constant Fraction Discriminators CFD8c CFD7x CFD4c CFD1c and CFD1x 11 0 1701 1...

Page 5: ...Constant Fraction DiscriminatorsCFD8b CFD4b and CFD1b 11 0 1701 1 Page 5 of 25...

Page 6: ...odules containing such boards please review first Chapters 3b 1 to 3b 3 and then refer to Chapter 3b 7 to learn about the difference between the standard CFD and the RoentDek bCFD settings 3b 1 Genera...

Page 7: ...weight 0 8 kg with an external 12 V DC mains adapter for use with 100 250 V AC sockets The power consumption is max 0 5 A at 12 V DC 6 W or max 0 7 A at 12 V DC 10 W for the CFD1x The CFD4c has the s...

Page 8: ...fraction is determined by the choice of fix resistors or a potentiometer as in case of the RoentDek CFDs While one of the signals is inverted later on the other experiences a certain delay CFD delay...

Page 9: ...he signals have to be verified on an oscilloscope The CFD Fraction can be adjusted by another potentiometer labelled Fr on the front panel CFD4b CFD1b side panel CFD8b top lid see Figure 3 6b Figure 3...

Page 10: ...s damped by a factor of 10 For achieving the ideal settings it is first of all important to note that the CFD operates best in all respects and yields the optimal temporal resolution if the input sign...

Page 11: ...delay D of 5 5 ns Note that the RoentDek CFDs will not operate without connecting an external delay cable bridge If the pulse rise time RT is defined as the time from reaching 10 to 90 of the signal m...

Page 12: ...livers the CFD with a standard CFD fraction setting of about 0 35 The CFD fraction can be varied between 0 15 and 1 via a potentiometer In order to observe and quantify the CFD fraction ratio on the o...

Page 13: ...during the bipolar signal s crossover while fluctuating almost equally between high and low states before and long after the signal due to electronic noise on the line not visible in the pictures If...

Page 14: ...idth bridges of the internal circuit see Figure 3 5b With the jumper in place the maximum width is increased to 2000 ns Please contact RoentDek if you are in need of the optional jumpers Obviously a s...

Page 15: ...15b Trace of the input signal to the Veto socket upper trace and signal traces of CFD timing signals lower trace integrated over many events for Veto left and Gating mode right In order to work reliab...

Page 16: ...he front panel 3b 4 2 Accessing the jumpers in CFD8c and CFD7x I Disconnect the mains power supply II On the rear panel remove all five screws red circles Please note that different types and sizes of...

Page 17: ...ear front panel and fix them with all screws and hex bolts 3b 4 3 Accessing the jumpers in CFD4c I Remove all six screws from the right side panel marked in red see Figure 3 20b Figure 3 20b Side pane...

Page 18: ...oscope see Figure 3 21b If a CFD is used for operating a RoentDek delay line detector or similar device these pre trigger events result in a distinct structure in the time sum spectrum see Figure 3 21...

Page 19: ...neighbours 3b 6 The CFDx pulse height determination option The CFDx function is an add on circuit that allows measuring the signal s pulse height The pulse height information is coded as a time delay...

Page 20: ...er trace ramp monitor output the Ramp switch is turned off here Signals are triggered on the CFD timing output signal trace not shown Left and right pictures were obtained with two different cable len...

Page 21: ...Dx signal This is indicated in Figure 3 26b The ramp slope is about 1 V per 12 ns giving an almost linear correspondence between pulse height and time delay with a typically 10 to 20 ns offset for pul...

Page 22: ...iming signal with a RoentDek TDC8HP The same spectrum could be recorded by plotting the time difference between trailing and leading transitions of the CFDx output It is advisable to mark the pulse he...

Page 23: ...se heights will not be registered Please contact RoentDek for advice unless you have received a properly matched system with bFAMP for a certain delay line read out anode Timing signals off the MCP co...

Page 24: ...3 12B SIGNAL TRACES AS IN FIGURE 3 8B LEFT WITH THE WALK LEVEL SET TO THE BASELINE OF THE INPUT SIGNALS LEFT PICTURE AND SLIGHTLY TOWARDS THE POSITIVE SIDE WHERE THE NOISE TRIGGERS BEGIN TO VANISH RIG...

Page 25: ...DTH POTENTIOMETER SETTING LOWER TRACE RAMP MONITOR ALL TRACES TRIGGERED ON THE STOP SIGNAL THE STOP SIGNAL SHOULD BE USED IF THERE IS A SPARE TDC CHANNEL AVAILABLE 21 FIGURE 3 27B AS FIGURE 3 25B RIGH...

Reviews: