Programming and Parameters
2-13
SPEED COMMA
N
D
Speed Re
fe
rences
096
[TB Man Ref Sel]
Sets the manual speed reference source
when a digital input is configured for
“Auto/Manual.”
(1)
“Analog In 2” is not a valid selection if it
was selected for any of the following:
- [Trim In Select]
- [PI Feedback Sel]
- [PI Reference Sel]
- [Current Lmt Sel]
- [Sleep Wake Ref]
Default:
Options:
1
1
2
3-8
9
“Analog In 1”
“Analog In 1”
“Analog In 2”
(1)
“Reserved”
“MOP Level”
097
[TB Man Ref Hi]
Scales the upper value of the [TB Man
Ref Sel] selection when the source is an
analog input.
Default:
Min/Max:
Units:
[Maximum Speed]
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
098
[TB Man Ref Lo]
Scales the lower value of the [TB Man Ref
Sel] selection when the source is an
analog input.
Default:
Min/Max:
Units:
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
Disc
re
te
Spee
ds
100
[Jog Speed 1]
Sets the output frequency when Jog
Speed 1 is selected.
Default:
Min/Max:
Units:
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
101
102
103
104
105
106
107
[Preset Speed 1]
[Preset Speed 2]
[Preset Speed 3]
[Preset Speed 4]
[Preset Speed 5]
[Preset Speed 6]
[Preset Speed 7]
Provides an internal fixed speed
command value. In bipolar mode direction
is commanded by the sign of the
reference.
Default:
Min/Max:
Units:
5.0 Hz/150 RPM
10.0 Hz/300 RPM
20.0 Hz/600 RPM
30.0 Hz/900 RPM
40.0 Hz/1200 RPM
50.0 Hz/1500 RPM
60.0 Hz/1800 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
108
[Jog Speed 2]
Sets the output frequency when Jog
Speed 2 is selected.
Default:
Min/Max:
Units:
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
Speed T
ri
m
116
[Trim % Setpoint]
Adds or subtracts a percentage of the
speed reference or maximum speed.
Dependent on the setting of parameter
118 [Trim Out Select].
Note: Added for firmware version 3.001.
Default:
Min/Max:
Units:
0.0%
–/+200%
0.1%
117
[Trim In Select]
Specifies which analog input signal is
being used as a trim input.
Default:
Options:
2
“Analog In 2”
File
Gr
oup
No.
Parameter Name & Description
Values
Related