2-12
Programming and Parameters
SPEED COMMA
N
D
Spd Mode/L
imits
087
[Skip Freq Band]
Determines the bandwidth around a skip
frequency. [Skip Freq Band] is split,
applying 1/2 above and 1/2 below the
actual skip frequency. The same
bandwidth applies to all skip frequencies.
Default:
Min/Max:
Units:
0.0 Hz
0.0/30.0 Hz
0.1 Hz
088
[Speed/Torque Mod]
Selects the torque reference source.
“Speed Reg” (1) - drive operates as a
speed regulator.
Default:
Options:
1
1
“Speed Reg”
“Speed Reg”
454
[Rev Speed Limit]
Sets a limit on speed in the negative
direction. Used in bipolar mode only. A
value of zero disables this parameter and
uses [Min Speed] for minimum speed.
Default:
Min/Max:
Units:
0.0 RPM
–[Max Speed]/0.0 Hz
–[Max Speed]/0.0 RPM
0.0 Hz
0.0 RPM
Spe
ed Ref
erenc
es
090
[Speed Ref A Sel]
Selects the source of the speed reference
to the drive unless [Speed Ref B Sel] or
[Preset Speed 1-7] is selected.
(1)
See Installation Manual for DPI port
locations.
Default:
Options:
2
1
2
3-8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
“Analog In 2”
“Analog In 1”
“Analog In 2”
“Reserved”
“MOP Level”
“Reserved”
“Preset Spd1”
“Preset Spd2”
“Preset Spd3”
“Preset Spd4”
“Preset Spd5”
“Preset Spd6”
“Preset Spd7”
“DPI Port 1”
(1)
“DPI Port 2”
(1)
“DPI Port 3”
(1)
“DPI Port 4”
(1)
“DPI Port 5”
(1)
thru
thru
thru
thru
thru
091
[Speed Ref A Hi]
Scales the upper value of the [Speed Ref
A Sel] selection when the source is an
analog input.
Default:
Min/Max:
Units:
[Maximum Speed]
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
092
[Speed Ref A Lo]
Scales the lower value of the [Speed Ref
A Sel] selection when the source is an
analog input.
Default:
Min/Max:
Units:
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
093
[Speed Ref B Sel]
.
Default:
Options:
11
“Preset Spd1”
See
094
[Speed Ref B Hi]
Scales the upper value of the [Speed Ref
B Sel] selection when the source is an
analog input.
Default:
Min/Max:
Units:
[Maximum Speed]
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
095
[Speed Ref B Lo]
Scales the lower value of the [Speed Ref
B Sel] selection when the source is an
analog input.
Default:
Min/Max:
Units:
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
File
Gr
oup
No.
Parameter Name & Description
Values
Related