Access Procedures
3-5
Installing the DPI / HIM
Assembly
Install the DPI / HIM assembly in reverse order of removal, while referring
to
Torque Specifications on page 3-2
.
Removing the 700S Phase I
Control Assembly
1.
Remove power from the drive. Refer to
Removing Power from Drive on
page 3-3
.
Important:
Before removing connections and wires, mark the connections
and wires to avoid incorrect wiring during assembly.
Important:
Minimum inside bend radius for SynchLink fiber-optic cable is
25.4 mm (1 in.). Any bends with a shorter inside radius can
permanently damage the fiber-optic cable. Signal attenuation
increases with decreased inside bend radii.
1.
Loosen the captive screw and swing the Control assembly away from
drive.
2.
On the Control assembly:
–
Unplug the I/O and SynchLink cables from the Main Control circuit
board
–
Unplug the feedback wiring from Feedback Option card
–
Unplug communication cables from DriveLogix™ controller (if
present)
3.
Unplug the ribbon cables from J2 and J7 on the Main Control circuit
board.
Note
: If the DriveLogix option is installed, the J2 and J7 connections for
the ribbon cables will be located behind the DriveLogix controller.
!
ATTENTION:
Hazard of permanent eye damage exists when
using optical transmission equipment. This product emits intense
light and invisible radiation. Do not look into fiber-optic ports or
fiber-optic cable connectors.
Summary of Contents for powerflex 700h
Page 4: ...soc ii Summary of Changes Notes ...
Page 8: ...4 ...
Page 46: ...2 14 Component Test Procedures ...
Page 92: ...3 46 Access Procedures Notes ...
Page 98: ...A 2 Service Tools and Equipment Notes ...
Page 106: ...B 8 Schematics Notes ...
Page 116: ...C 10 Disassembly Assembly Diagrams Notes ...
Page 119: ......