1-12
Troubleshooting and Error Codes
88
Stahl Optics
Linear Stahl Encoder detected a
fault. Parameter 291 [Lin1Stahl
Status] shows the details of the fault.
•
Reconnect encoder or replace
encoder.
•
Reconnect option feedback card.
93
+/- 12volt Power
Alarm
The12V DC control voltage is outside
the tolerance range (Alarm). The
positive voltage power exceeds
+15.50 V DC. The negative voltage
power exceeds -15.50V DC.
•
Check the power supply on the
High Power Fiber Optic Interface
and Voltage Feedback boards
94
Analog In 1 Loss
Analog Input channel 1 is lost. For
configuration of Analog Input channel
1, see parameter 1093 [Anlg
In1LossCnfg].
•
Check condition of Analog Input
channel 1.
•
Change configuration for [Anlg
In1LossCnfg].
95
Analog In 2 Loss
Analog Input channel 2 is lost. For
configuration of Analog Input channel
2, see parameter 1094 [Anlg
In2LossCnfg].
•
Check condition of Analog Input
channel 2.
•
Change configuration for [Anlg
In2LossCnfg].
96
Analog In 3 Loss
Analog Input channel 3 is lost. For
configuration of Analog Input channel
3, see parameter 1095 [Anlg
In3LossCnfg].
•
Check condition of Analog Input
channel 3.
•
Change configuration for [Anlg
In3LossCnfg].
129 Faults Cleared
Indicates that all faults have been
cleared.
*Informational only.
130 Fault Q Cleared
Indicates that the fault queue has
been cleared.
*Informational only.
131 Alarm Cleared
Indicates that all alarms have been
cleared.
*Informational only.
132 Alarm Q Cleared
indicates that the alarm queue has
been cleared.
*Informational only.
No. Name
Description
Action
(if appropriate)
Summary of Contents for powerflex 700h
Page 4: ...soc ii Summary of Changes Notes ...
Page 8: ...4 ...
Page 46: ...2 14 Component Test Procedures ...
Page 92: ...3 46 Access Procedures Notes ...
Page 98: ...A 2 Service Tools and Equipment Notes ...
Page 106: ...B 8 Schematics Notes ...
Page 116: ...C 10 Disassembly Assembly Diagrams Notes ...
Page 119: ......