Troubleshooting the Drive Using the OIM
7-5
Faults can also be reset without clearing the fault log by:
•
Pressing
when the drive is stopped and the control source is set to OIM.
•
Asserting fault reset from the selected control source.
To reset the faults and clear the fault log:
Step 1. Select Clear Fault Log and Reset Faults from the Fault Menu. Press
.
Step 2. The message “ATTENTION! DRIVE FAULTS HAVE BEEN RESET. FAULT
LOG HAS BEEN CLEARED” is displayed. The FAULT indicator is turned off,
the faults are reset, and the fault log is cleared.
Step 3. Press
to return to the Fault Menu.
Step 4. Press
again to return to program or monitor mode.
Important: You cannot clear individual faults. This procedure clears the entire fault
log.
7.3
Reviewing Active Alarms Using the Alarm Menu
You can review active alarms using the Alarm Menu. Alarms are not logged.
To review active alarms:
Step 1. Press
until ALARM is displayed in the key indicator. The screen
shown in figure 7.6 is displayed.
Figure 7.6 – Alarm Menu