6-4
GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0
6.2
Selecting the Control Source
Use
to select the control source for the drive.
The control source can be set to one of four options:
•
LOCAL: The drive’s front panel keypad/display is used to control the drive.
•
TERMBLK: The signals at the Regulator board terminal strip control the drive.
•
OPTION: An option board, such as the AutoMax Communication Network board, controls
the drive.
•
OIM: The OIM keys control the drive.
To select the control source:
Step 1. Stop the drive if it is running.
Step 2. Press
. The CONTROL SOURCE SELECT screen is displayed, as shown
in figure 6.4.
Step 3. Use
or
to move the cursor to the control source your want.
Step 4. Press
to accept the new control source and return to the previous
screen.
When the control source is changed to OPTION or TERMBLK,
is
automatically set to AUTO. When the control source is changed from OPTION or
TERMBLK to OIM or LOCAL,
is automatically set to MANUAL. When the
control source is changed from OIM to LOCAL or vice versa, the
setting is not
changed.
Figure 6.4 – CONTROL SOURCE SELECT Screen
Summary of Contents for Reliance electric GV3000/SE
Page 6: ...IV GV3000 SE Operator Interface Module OIM User Guide Version 2 0 ...
Page 8: ...VI GV3000 SE Operator Interface Module OIM User Guide Version 2 0 ...
Page 12: ...1 4 GV3000 SE Operator Interface Module OIM User Guide Version 2 0 ...
Page 20: ...2 8 GV3000 SE Operator Interface Module OIM User Guide Version 2 0 ...
Page 87: ...A 18 GV3000 SE Operator Interface Module OIM User Guide Version 2 0 ...
Page 101: ...B 14 GV3000 SE Operator Interface Module OIM User Guide Version 2 0 ...
Page 111: ......