Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 2017
PowerFlex 753 Drive (P_PF753)
For the PowerFlex 753 Drive Instruction, the Invalid Configuration indicator
appears under the following conditions:
•
The Fail to Start check time, Fail to Stop check time, Reset Pulse time, or
Maximum Jog time is set to a value less than zero or greater than 2,147,483
seconds.
•
The Speed Feedback Raw Minimum and Raw Maximum scaling
parameters are set to the same value.
•
The Speed Feedback Scaled EU Minimum and EU Maximum scaling
parameters are set to the same value.
•
The Speed Reference Raw Minimum and Raw Maximum scaling
parameters are set to the same value.
•
The Speed Reference Scaled EU Minimum and EU Maximum scaling
parameters are set to the same value.
•
The Maximum Speed Reference clamp value is less than the Minimum
Speed Reference clamp value, or either clamp value is less than zero.
•
The Simulated Timer Preset is set to a value less than zero or greater than
2,147,483 seconds.
•
An Alarm Minimum On Time or Shelf Time is set to a value less than zero
or greater than 2,147,483 seconds.
•
Alarm Severity is set to a value less than 1 or greater than 1000.
For the PowerFlex 753 Drive Instruction, the Device Not Ready indicator
appears under the following conditions:
•
Device has been disabled by Maintenance.
•
There is a configuration error.
•
Interlock or Permissive is not OK.
•
Operator State 0 priority command requires reset.
•
Device Failure and shed requires reset.
•
I/O Fault and shed requires reset.
•
Device has tripped (Device Fault).
•
Drive is not ready.
•
Device logic is disabled or there is no mode.
TIP
When the Invalid Configuration Indicator appears, you can find what
configuration setting is invalid by following the indicators. Click the graphic
symbol to open the faceplate. The Invalid Configuration indicator appears next
to the appropriate tab at the top of the faceplate to guide you in finding the
configuration error. Once you navigate to the tab, the misconfigured item is
flagged with this indicator or appears in a magenta box.
TIP
When the Device Not Ready indicator appears, you can find what condition is
preventing operation by following the indicators. Click the graphic symbol to
open the faceplate. The Device Not Ready indicator appears next to the
appropriate tab at the top of the faceplate to guide you in finding the
condition. When you navigate to the tab, the condition preventing operation is
flagged.