Chapter
Set-up Procedures: SMP PLUS
Controller without Options
3-6
3
Customer Settings (continued)
This mode is used for applications requiring across the line starting. The ramp time
is set for less than 1/4 second as shown in Figure 3.8.
Figure 3.8 - Full Voltage
100
Time (seconds)
Percent
Voltage
Full Voltage Start Selection without Options
Refer to Figure 3.9.
1.
Starting Time – For full voltage starting, switches 7–9 must be OFF. This
results in a ramp period of less than 1/4 second
2.
Kickstart Time – Set Kickstart Time rotary digital switch to OFF
3.
Initial Torque – Set Initial Torque rotary digital switch to 9
4.
Current Limit/Soft Start – For full voltage starting, switch 6 must be OFF
5.
Energy Saver Select – Switch 5 must be OFF. Energy Saver is not available
6.
Auxiliary Contact Select – Set switch 4 OFF if you want “normal” auxiliary
contacts, ON if you want “up-to-speed” auxiliary contacts.
7.
Stall Select – Set switch 3 ON if you want the stall feature (or OFF if you do
not want this feature active)
NOTE:
For resistive load operation, switch 3 must be OFF
Figure 3.9 - Set-up Procedure for Full Voltage (without Options)
Switch
TIME (seconds)
Number
1/4
9
Off
8
Off
7
Off
6
Off
5
ENERGY SAVER SELECT
4
AUXILIARY CONTACT SELECT
3
STALL SELECT
2
NOT USED
1
NOT USED
Initial Torque
Position
0
1
2
3
4
5
6
7
8
9
% of Locked Rotor Torque
5
10
20
30
40
50
60
70
80
90
Kickstart Time
Position
0
1
2
3
4
5
6
7
8
9
Time (Sec.)
Off
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Full Voltage
Starting
Full Voltage Start
Selection without
Options