a.
Select the drive rating
b.
Set the firmware revision
c.
Set the Electronic Keying
d.
Configure the Input and Output Datalinks
e.
Create Database from the online drive or download from the web.
The PowerFlex 525 Add-On Profile provides the ability to configure Up to 4 words of Input Data and 4 words of
Output Data can be defined for the embedded Ethernet connection. By default, drive status and control
information will be communicated. The PowerFlex 525 allows datalinks to be configured to drive parameters.
Status Information
The “DriveStatus” word contains the drive status bit information, such as Ready, Fault, and At Reference.
The “OutputFreq” word contains the speed feedback information, which shows the actual operating frequency
(Hz) of the drive.
Control Information
The “LogicCommand” word contains the drive command bit information, such as Stop, Start, Forward, Reverse,
and Clear Faults.
The “FreqCommand” word contains the commanded reference value for the drive to run.
Datalinks
Datalinks are pointers to drive and/or other port parameters. Instead of offering fixed I/O assemblies where what-
you-see-is-what-you-get, our drive I/O assembly is dynamic and gives the programmer the ability to pick & choose
the desired parameters to communicate as network I/O.