A-4
Supplemental Information
PowerFlex Diode Bus Supply User Manual
Publication 20T-UM001D-EN-P
AC Input Fusing
below provides output ampere ratings for the Diode Bus Supply
(including continuous, 1 minute, and 3 seconds) and recommended AC line
input fusing information. The short circuit protection fuses are acceptable
for UL and IEC requirements. Sizes listed are recommended sizes based on
40 °C (104 °F) and the U.S. NEC. Other country, state or local codes may
require different ratings.
Fuse Types
Refer to the recommended types listed below.
•
IEC – BS88 (British Standard) Parts 1 & 2
(1)
, EN60269-1,
Parts 1 & 2, type gG or equivalent should be used.
•
UL – UL Class RK1 or J must be used.
(2)
Table A.A AC Input Current Ratings and Recommended Input Fusing
(1)
Typical designations include, but may not be limited to, the following; Parts 1 & 2:
AC, AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, and GH.
(2)
For 600V, (Ferraz Shawmut) Class J: AJT150 (with open fuse indicator),
Class RK1: A6D150R
(Bussman)
Class J: LPJ-150SP,
Class RK1: LPS-RK-150SP or equivalent
Bus Supply
Catalog
Number
Input Ratings Output Amps
Dual Element
Time Delay Fuse
Amps
kVA
Cont.
1 Min. 3 Sec. Amps
240 Volt / 60 Hz AC Input
125
IEC - gG
or
150
UL - Class RK1 or J
20TD120
105
44
120
180
240
400 Volt / 50 Hz AC Input
20TD120
105
73
120
180
240
480 Volt / 60 Hz AC Input
20TD120
105
87
120
180
240
500 Volt / 50 Hz AC Input
20TE120
105
91
120
180
240
600 Volt / 60 Hz AC Input
20TE120
105
109
120
180
240