Maintain and Troubleshoot the MobileView Terminal and IP65 Junction Box
Chapter 6
Real-time Clock Battery
The MobileView 2711T terminal uses nonvolatile memory that requires a
real-time clock (RTC) lithium battery to retain system information when power
is removed. The battery has a 17-year life.
The RTC battery is soldered to the main circuit board, non-serviceable, and
therefore not intended to be replaced during the life of the MobileView 2711T
terminal.
Troubleshoot the
MobileView 2711T Terminal
The following table lists possible anomalies that can occur with your terminal
and solutions to the anomalies.
Anomaly
Solution
Page
Terminal does not power up
Check for 24V DC power on the connector of the MobileView junction box.
• For 2711T-JBIP20DC, the IP20 junction box: Check the terminal connections at X1 and X2 of the junction
box.
• For 2711T-JBIP65DC1, the IP65 junction box with cord grip connections: Check the power connections
at the S16 terminal of the junction box.
• For 2711T-JBIP65DM1, the IP65 junction box with M12 On-Machine™ connections: Check for a solid
connection between the power supply cable and the cable connection on the junction box.
Check for a solid connection between the MobileView connection cable and the cable connection of the
junction box.
For IP20 junction boxes
For IP65 junction boxes
Check the terminal connections to the main control board of the MobileView 2711T terminal.
Terminal screen is dim or black
If the screen is readable:
a. Adjust the screen brightness at the bottom of the window that appears.
a. From the MobileView terminal desktop, tap Power Options.
If the screen is black:
• Tap the touch screen or any of the keypad buttons to de-activate the screen saver.
• Check power to the terminal. Follow instructions for anomaly, ‘Terminal does not power up.’
• If the screen is blinking or rapidly changing brightness, a corrupted registry or OS image can exist.
a. Restore the OS image.
b. If an OS image restoration does not correct the anomaly, contact Rockwell Automation® Technical
Support.
Difficulty with touch screen selections
The touch screen can be out of alignment. Recalibrate the touch screen.
Terminal screen is static (locked up).
Touch screen and keypad activations do not initiate any
changes.
Check Ethernet communications. See the next anomaly, ‘Terminal does not communicate on Ethernet
network.’
Terminal does not communicate on Ethernet network
Check Ethernet cable connections at the MobileView junction box and your Ethernet hub.
For IP20 junction boxes
For IP65 junction boxes
Try to ping the MobileView 2711T terminal from a personal computer in your network to check for correct
configuration settings, then check MobileView 2711T terminal settings.
If you are using a DHCP server, check if the DHCP function is set in the network settings of the MobileView
2711T terminal.
If you connect to the Ethernet network with fixed settings, verify that the IP address, subnet mask, and
default Gateway-network settings are correct in the MobileView 2711T terminal.
Check the Ethernet connection on the MobileView 2711T terminal.
Program memory low
From the terminal desktop, tap File Explorer. Use File Explorer to clean up or delete unnecessary files.
An error message alerts you to install Windows
Power to the MobileView terminal was temporarily interrupted during the Windows setup process. Restore
the OS image with an image file downloaded from the Rockwell Automation PCDC site.
The Windows OS image is corrupt
Restore the OS image from a backed up image or with an image file downloaded from the Rockwell
Automation PCDC site.
Summary of Contents for Allen-Bradley MobileView 2711T-VMBRACKET
Page 6: ...6 Rockwell Automation Publication 2711T UM001E EN P March 2019 Table of Contents Notes ...
Page 14: ...14 Rockwell Automation Publication 2711T UM001E EN P March 2019 Chapter 1 Features Notes ...
Page 100: ...100 Rockwell Automation Publication 2711T UM001E EN P March 2019 Index Notes ...
Page 101: ...Rockwell Automation Publication 2711T UM001E EN P March 2019 101 Index Notes ...
Page 102: ...102 Rockwell Automation Publication 2711T UM001E EN P March 2019 Index Notes ...
Page 103: ......