Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012
49
Use a PowerFlex 70 Drive in an RSLogix 5000 Project
Chapter
3
5.
Change the
Local_DeviceNet_scanner_N01_
POL_O.Reference tag to 15000.
This value is the speed to which
your drive accelerates.
6.
Change the
Local_DeviceNet_scanner_N01_
POL_O.Start tag to 1.
The display on the drive registers
the speed increase in Hertz until the value entered at the reference tag is reached.
7.
Change the O.Start tag back to 0.