Rockwell Automation Publication 1502-UM060A-EN-P - October 2020
41
Chapter 4 Maintenance
Figure 27 - Closing the Contactor
4. After the top screw is finger tight, continue to tighten this screw with a
hand tool. The armature stop bracket flexes a little, which is acceptable,
but do not overtighten and bend the armature stop plate. It is important
that the armature plate is held tightly against the magnet cores. The
contactor must be fully closed.
5. Place a wide blade 0.030 in. (0.76 mm) feeler gauge between the plastic
auxiliary actuator tips and the steel actuator plate. To aid the installation
of the feeler gauge, the gauge can be put in place as the clamping block
screw is being finger-tightened (Step 3). See
and
.
Figure 28 - Gauging the Contacts