14
Rockwell Automation Publication 1502-UM060A-EN-P - October 2020
Chapter 1 Product Description
Table 4 - Contactor Coil Data
Control Voltage (V
CTL
)
Coil Voltage (V
CL
)
Electromechanical Relay Controlled (Electrically Held)
120V AC
110V DC
Close current inrush
7.3 A
DC
Economized holding current
0.13 A
DC
Minimum CR1 coil pick-up voltage
102V AC
CR1 coil drop-out voltage
75V AC
Electromechanical Relay Controlled (Electrically Held)
230V AC
210V DC
Close current inrush
8.3 A
DC
Economized holding current
0.11 A
DC
Minimum CR1 coil pick-up voltage
190V AC
CR1 coil drop-out voltage
140V AC
Electromechanical Relay Controlled (Mechanical Latch)
120V AC
110V DC
Close current inrush (A
DC
)
5.6 A
DC
Pilot Relay (CR1) pick-up voltage
102V AC
Minimum trip coil voltage
84V AC
Trip coil current
6 A
Electromechanical Relay Controlled (Mechanical Latch)
230V AC
210V DC
Not available at this control voltage
Table 5 - Operational Characteristics
Mechanical life
(1)
(1)
Provided that regular maintenance is performed, as detailed in this manual.
Electrically held
2,500,000 operations
Mechanical latch
100,000 operations
Electrical life
(1)
1,000,000 operations
Switching frequency
Electrically held
600,000 operations per hour
Mechanical latch
150,000 operations per hour
Table 6 - Opening and Closing Times
IntelliVAC Control (Electrically Held & Mechanical Latch)
Maximum closing time (50…60 Hz)
120 / 240V AC
100/70 ms
Maximum opening time (without delay, for 50…60 Hz)
(1)
(1)
A contactor drop-out delay may be configured with the IntelliVAC control module, publication
60 ms
Electromechanical (Relay) Controlled
Maximum closing time (120V AC)
(2)
(2) Control/Pilot relay, other than the standard Rockwell Automation Control Panel assembly (1503C-E4_ or 1503C-M4D), must
provide a constant closing signal for at least this period of time. The use of control components other than Rockwell
Automation products is not recommended and may pose reliability concerns.
50/60 Hz
160 ms
Maximum opening time (120V AC)
(3)
(3) Mechanical latched.
50 ms
Maximum opening time (120V AC)
(4)
(4) Electrically held, normal dropout.
160 ms
Table 7 - Capacitor Switching
System Voltage
2400V
800 KVAR
4160V
1400 KVAR
6900V
2000 KVAR