![Rockwell Automation Allen-Bradley G Series User Manual Download Page 12](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-g-series/allen-bradley-g-series_user-manual_1475408012.webp)
12
Rockwell Automation Publication 1502-UM060A-EN-P - October 2020
Chapter 1 Product Description
Catalog Number
Explanation
The following catalog number explanation is used to identify the contactor and
must be used when contacting your local Rockwell Automation sales office for
assistance.
Contactor Dropout Times
The IntelliVAC contactor control module (publication
speed at which the electrically held vacuum contactor opens.
When electromechanical relays are used to control the electrically held
contactor, there are two speeds available: normal dropout time and fast
dropout time. The opening speed is controlled by changes to the onboard
contactor control circuity (see
through
).
Contactors that are configured for faster dropout times are used for specific
applications if faster uncoordinated action is required.
Contactors with normal dropout times are used in coordination with medium
voltage power fuses. The dropout time must be longer than the Total Clearing
Time of the medium voltage power fuses being applied in combination with
the vacuum contactor. Damage to the contactor can occur if this coordination
is not addressed appropriately.
All mechanically latched contactors are designed with the fast dropout time.
1502
–
V
4
–
D
-
B
-
D
-
A
-
0
a
b
c
d
e
f
g
a
b
c
d
Contactor Type and Interlock
Contactor Size
Nominal Line Voltage
Control Circuit
(1)
Code
Description
Code
Description
Code
Description
Code
Description
V
Vacuum, electromechanical relay
controlled
4
450 A
D
7200V
B
5000V
VC
Vacuum, optimized for IntelliVAC control
C
7200V
(1)
Or voltage transformer primary fuse mounting provisions.
b
c
d
Coil Voltage
Function
Altitude Code (m)
Code
Description
Code
Description
Code
Description
D
110V DC
A
3-pole, electrically held contactor
0
-1000…5000
E
207V DC
B
3-pole, mechanically latched contactor with
electrical and mechanical release
D
3-pole, electrically held contactor with
fast drop-out
(1)
(1)
Controlled by electromechanical relay.