Chapter 1 Product Description
Contactor Identification
Each contactor is identified with a rating label (
) attached to the
armature plate at the front of the contactor. The rating label information
includes the Catalog Number (Cat.) Series Letter (Ser.) Voltage Rating, Non-
Enclosed Current Rating, Interrupting Capacity, Altitude Range (in meters),
CSA, UL, and CE markings.
Figure 4 - Contactor Rating Label (450 A)
WARNING:
The Rockwell Automation® relay control panel (1503C-XXX or
1503E-CXXX) is required for reliable operation of the contactor within
its published specifications. The relays break the DC current that is
drawn by the closing coil, holding coil, and trip coil. The relays make
sure the pick-up and drop out voltages are coordinated with the pick-
up and drop out voltages of the contactor. This provides reliable
operation of the circuit in undervoltage conditions. The use of
alternative control relays is not supported or recommended. Alternative
relays do not provide the necessary control timings necessary to
provide reliable operation and coordination with all power fuses used in
combination with the contactors.